ZW32-24 outdoor MV vacuum circuit breaker (Hereinafter referred to as the circuit breaker) is outdoor distribution equipment with rated voltage 24KV, three phase AC 50Hz. It is mainly used for breaking and closing the load current, overload current and short circuit current of power system. Applied to substation and industrial and mining enterprises in power system for protection and control use, more suitable for rural power grid and the frequent operation place.
ZW32-24 outdoor MV vacuum circuit breaker (Hereinafter referred to as the circuit breaker) is outdoor distribution equipment with rated voltage 24KV, three phase AC 50Hz. It is mainly used for breaking and closing the load current, overload current and short circuit current of power system. Applied to substation and industrial and mining enterprises in power system for protection and control use, more suitable for rural power grid and the frequent operation place.
Model Meaning
ZW
32
24
1
T
630
20
G
□
↓
↓
↓
↓
↓
↓
↓
↓
Outdoor
Vacuum
Circuit
Breaker
Design
sequence
number
Rated
voltage(kV)
Ammunition
handling
mechanism
Rated
current(A)
Rated
short circuit
breaking
current(kA)
Tape
isolation
S hand
exercise
Delectric
exercise
Quoted Standard
1. GB 1984-2003 AC high voltage circuit breaker
2. GB 3309-1989 Mechanical test of high voltage switchgear at room temperature
3. GB 5582-1993 The pollution level of insulating high voltage electric power equipment
4. GB 1985-2004 AC high voltage isolation switch and earthing switch
5. GB/T 11022-1999 Common technical requirement for high voltage switch equipment and control equipment standard
6. GB 16927.1-1997 The first part of high voltage test techniques: General test requirements
7. DL/T 402-2007 Technical conditions for AC high voltage circuit breaker order
8. DL/T 593-2006 The common technical specification of high voltage switch equipment and control equipment standards
Main Technical Parameters
Rated voltage
kV
24
Rated insulation
level
1 min power
frequency withstand
voltage
Dry test
kV
65/79(isolation fracture)
Wet test
kV
50/64(isolation fracture)
The auxiliary circuit and control circuit
kV
2
Lightning impulse withstand voltage (peak)
kV
125/145(isolation fracture)
Rated frequency
Hz
50
Rated current
A
6301250
Rated operating sequence
O-0.3s-CO-180s-CO
Rated short-circuit breaking current
kA
16 20
25
Rated short-circuit closing current(peak)
kA
40 50
63
Rated peak withstand current
kA
40 50
63
Rated short-time withstand current
kA
16 20
25
Rated short circuit duration
S
4
Rated short-circuit breaking current times
Times
20/25
Breaking Times of rated current
Times
10000
Closing time
ms
20~80
Under maximum operating voltage
ms
20~80
Opening time
Under rated operation voltage
ms
20~80
Under lowest operating voltage
ms
20~80
Full off time
Times
≤100
Mechanical life
J
10000
Switch on power
W
70
Energy storage motor rated input power
V
≤70
Rated operational voltage and auxiliary circuits rated voltage
V
DC,AC 220
Energy storage time under rated voltage
S
≤8
Overcurrent release
Rated current
A
5
Tripping current accuracy
%
±10
Circuit Breaker After Assembly And Adjustment Should Meet The Requirements Of Table 2
ltem
Unit
Parameter
Open clearance between contacts
mm
13±1
Contact overtravel
mm
3±1
Average opening speed
m/s
1.5±0.2
Average closing speed
m/s
0.8±0.2
Contact closing bounce time
ms
≤3
Three-phase tripping over the same period of time
ms
≤2
DC resistance of circuit for every phase(with isolating switch)
μΩ
≤60(150)
Allowable wear thickness for dynamic and static contact
1. Ambient air temperature: The daily temperature variation: -40℃ ~+40℃ diurnal variation of temperature less than 25℃;
2. Altitude: no more than 2000 meters
3. Wind speed is no more than 35m/s (equivalent to 700Pa on the surface of the cylindrical);
4. Ice cover thickness no more than 10mm;
5. The intensity of sunshine not more than 1000W/m ²
6. Pollution degree no more than GB 5582 IV class
7. Seismic intensity does not exceed 8 class
8. No flammable, explosive, chemical corrosion and severe vibration place
9. the conditions of use exceed the above-mentioned regulations, it shall be determined through consultation between the user and the manufacturer.
Dimensions
Overall And Mounting Dimensions (mm)
1. lower outlet
2. current transformer
3. Upper Inlet
4. Insulating pillar
5. The vacuum interrupter
6. wire guides
7. flexible connection
8. Insulated tension pole
9. actuator
10. case