...

ZN63A(VS1)-12 Indoor High Vacuum Circuit Breaker

ZN63(VS1)-12 type indoor high-voltage vacuum circuit breaker, a three-phase AC 50Hz rated voltage of 12kV power system indoor switching equipment, as the power grid equipment, industrial and mining enterprises power equipment protection and control unit. Suitable for frequent operation at rated operating current, or multi-alternating short-circuit current.

The circuit breaker adopts the integrated design of the operating mechanism and the circuit breaker body, which can be used as a fi xed installation unit, and can also be equipped with a special propulsion mechanism to form a handcart unit.

Get A Quote Data Download
Product Overview

Overview

ZN63(VS1)-12 type indoor high-voltage vacuum circuit breaker, a three-phase AC 50Hz rated voltage of 12kV power system indoor switching equipment, as the power grid equipment, industrial and mining enterprises power equipment protection and control unit. Suitable for frequent operation at rated operating current, or multi-alternating short-circuit current.

The circuit breaker adopts the integrated design of the operating mechanism and the circuit breaker body, which can be used as a fi xed installation unit, and can also be equipped with a special propulsion mechanism to form a handcart unit.

 

Model Meaning

VS 1 12 1
Indoor high
voltage vacuum
circuit breaker
Product design serial number Rated voltage (KV) Rated current (A) Rated short circuit breaking current(kA)

 

Main Technical Parameters

Item Units Argument
Rated voltage kV 12
Rated insulation
level
Peak rated lightning impulse withstand voltage kV 75
1min power frequency withstand voltage 42
Rated short-circuit breaking current kA 20/25 31.5 40
Rated current A 630、
1250
630、1250、
1600、2000、
2500、3150
630、1250、1600、2000、
2500、3150
Rated thermal stable current(RMS) kA 20/25 31.5 40
Rated dynamic stable current (peak) 63 80 100
Rated short circuit closing current (peak) 63 80 100
Rated short circuit breaking current breaking times Number of times 50
Secondary circuit power frequency withstand voltage (Imin)s V 2000
Rated operating sequence O-0.3-CO-180s-CO
O-180s-CO-180s-CO
Rated thermal stability time S 4
Rated single/back-to-back capacitor bank breaking current A 630/400800/400(40kA)
Mechanical life Number of times 10000

 

External Mounting Dimension (mm)

 

Rated current(A) 630 1250 1600
Rated short circuit breaking current (A) 20/25 25/31.5 31.5

 

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
Get High And Low Voltage Power Transmission And Distribution Solutions Today !
X
icon
icon
icon