XGN15-12/24/36 Air Insulated RMU (Fixed Type)

XGN15-12/24/36 Air Insulated RMU (Fixed Type), used in rated voltage 12/24/36kV, rated current 630A and below the ring power supply or radiation power supply system, especially suitable for pre-installed substation as a power system control and protection. This product is equipped with FLN36-12D type sulfur hexafl uoride load switch or FLRN36-12D type load switch and disintegrator combination electrical appliances, with small size, light weight, easy operation, light operation force, reliable interlock, maintenance-free and other characteristics, is a new generation of high voltage switchgear required for urban power grid transformation and construction

Get A Quote Data Download
Product Overview

Overview

XGN15-12/24/36 Air Insulated RMU (Fixed Type), used in rated voltage 12/24/36kV, rated current 630A and below the ring power supply or radiation power supply system, especially suitable for pre-installed substation as a power system control and protection. This product is equipped with FLN36-12D type sulfur hexafl uoride load switch or FLRN36-12D type load switch and disintegrator combination electrical appliances, with small size, light weight, easy operation, light operation force, reliable interlock, maintenance-free and other characteristics, is a new generation of high voltage switchgear required for urban power grid transformation and construction.

This product complies with: GB3906 “3~35kV AC metal enclosed Switchgear”, GB/T11022 “High voltage switchgear and control equipment standard common technical requirements”, IEC298 “rated voltage above 1kV 50kV and below AC metal enclosed switchgear and control equipment”, DI/T404 “Indoor AC high voltage switch cabinet ordering technical specifi cations” standard.

 

Model Meaning

X G N 15 12/24/36 (F.R)
Box type Stationary Indoor Design sequence number Rated voltage Load switch-breaker combination appliance

 

Normal Service Condition

1 Ambient air temperature: -15℃ ~+40℃ ;

2 Altitude: 1000m and below;

3 Humidity conditions:The daily average value is not more than 95%, and the daily average water vapor pressure is not more than 2.2kPa; The monthly average value is not more than 90, and the monthly average water vapor pressure is not more than 1.8kPA.

4 Earthquake intensity: not more than 8 degrees;

5 There is no obvious pollution such as turbid or combustible gas.

Note: When the above normal conditions of use are exceeded, the user can negotiate with the company.

 

XGN15-12/24/36 Air Insulated RMU (Fixed Type)

Sr.No. Description Unit Value
1 Rated voltage(Ur) kV 12 24 36
2 Rated current(Ir) A 630 630 630
3 Rated frequency(fr) Hz 50 50 50
4 Rated short-time power-frequency withstand voltage/1min
(phase-to-phase &to-earth/across the isolating distance)
kV 28/32 50/60 70/80
5 Rated lightning impulse withstand voltage
(phase-to-phase &to-earth/across the isolating distance)
kV 75/85 125/145 170/195
6 Rated short-time withstand current kA/s 45741 45736 45673
7 Rated peak withstand current kA 62.5 50 40
8 Rated short-circuit making current kA 62.5 50 40
9 Rated transfer breaking current A 1700 1400 630
10 Rated closed-loop breaking current A 630 630 630
11 Maximum rated current of the fuse A 200 200 63
12 Main switch Mechanical endurance ops M2(5000) M2(5000) M1(1000)
13 Earthing switch ops M1(2000) M1(2000) MO(1000)
14 Electrical endurance 1 Class E3 Class E3 Class E3
15 IAC class 1 A-FLR
20kA/1s
25kA/1s
A-FLR
16kA/1s
20kA/1s
A-FLR
16kAV1s
16 Degree of protection 1 IP4X P4X IP4X

 