The TR8-1800I is a TUR distribution board designed for 1000 kVA transformer connections, making it the highest-capacity model in this range. Its dimensions are 1450 x 900 x 540 mm, with recommended fixing centres of 760 ± 20 mm horizontally and 590 mm vertically. It requires 4 x 240 mm² or 2 x 630 mm² aluminium cables per phase, and 2 x 240 mm² or 1 x 630 mm² for the neutral. For upstream connection, it uses three U-shaped interphase connection brackets and six connection plates, tightened to 30 ± 5 Nm. The 1800 A switch handle is connected with two M8x20 screws with captive washers in the right upright inserts. This model is intended for demanding high-power transformer-to-distribution connections.
Principaux paramètres techniques
Main mechanical parameters
| Objet |
Unité |
Paramètres |
|
| Courant nominal |
A |
1800 |
|
| Dimensions (H x W x D) |
mm |
1450 x 900 x 540 |
|
| Recommended Fixing Centers (H / V) |
mm |
760±20 / 590 |
|
| Fixing Holes |
– |
4 x M14 |
|
| Transformer Power |
kVA |
1000 |
|
| Recommended Cable per Phase (ALU) |
mm² |
4 x 240 or 2 x 630 |
|
| Recommended Neutral Cable (ALU) |
mm² |
2 x 240 or 1 x 630 |
|
| Fuse Type |
– |
T2 (115mm, 440V) |
|
| Barres de bus |
Nm |
N, Ph1, Ph2, Ph3 |
|
| Mounting Type |
– |
Wall-mounted |
|
| Switch Handle Position |
mm² |
Up=Closed(Red) / Down=Open(Green) |
|
| MALT Earthing Torque |
Nm |
30±5 |
|
| Handle Mounting Torque |
Nm |
2 x M8x20 |
|
| Upstream Connection Torque |
Nm |
30±5 |
|
| Side Panels Torque |
Nm |
30±5 |
|
| Monobloc Outgoing Feeder Torque |
Nm |
30±5 |
|
Functional Features:
-
Electrical function: suitable for a 1000 kVA transformer LV main incoming/main switch; switch rated current 1800 A.
-
Connection capability: recommended phase cable 4 × 240 mm² or 2 × 630 mm² Alu; neutral cable 2 × 240 mm² or 1 × 630 mm² Alu.
-
Operation: manual switch operation; handle up = CLOSED (red), down = OPEN (green); padlocking possible in the OPEN position; handle fixed with 2 M8x20 screws and captive washers into the right upright inserts.
-
Safety and protection: earthing connection; side panels, horizontal protection screen, removable screen to prevent direct contact with live parts.
-
Expansion: optional EP lighting, ACG general switch, reservation panel, monobloc outgoing units, fuse protection.
-
Difference: upstream connection requires 3 interphase U-shaped connecting brackets and 6 connection plates; horizontal protection screen mounted via a screen support bracket.
.