Choosing between 12kV, 24kV and 40.5kV metal-clad switchgear is one of the first decisions in any medium-voltage project — and one of the most expensive to get wrong. The metal clad switchgear voltage class determines insulation levels, busbar configuration, cabinet dimensions and, ultimately, the cost of your substation. This guide compares the three classes side by side, explains where each one fits, and walks through the selection checks our engineers apply when quoting metal-clad switchgear for utilities, EPC contractors and industrial plants.
The term appareillage de commutation à enveloppe métallique is sometimes used loosely, so it is worth fixing the definition before comparing voltage classes. Under IEC 62271-200, a metal-clad switchgear assembly encloses all live parts in earthed metal compartments, with internal metal barriers or partitions separating the busbar compartment, the circuit breaker compartment, the cable compartment and the low-voltage control compartment. The circuit breaker is mounted on a withdrawable truck, so it can be racked from the service position to a test or disconnected position without de-energising the busbar.
This is what distinguishes metal-clad construction from general metal-enclosed switchgear, where the enclosure is metallic but the internal segregation and withdrawable requirements are less stringent. In other words, withdrawable metal enclosed switchgear with full compartmentalisation is the defining feature of the metal-clad category — and it is exactly the construction used in the KYN28 and KYN61 platforms discussed below.
The three voltage classes cover the full medium-voltage range of IEC 62271-200 assemblies from distribution level up to sub-transmission. The table below summarises the rated insulation levels and typical service ranges. Note that the 40.5 kV class in GB/T 3906 corresponds to the 36 kV class in IEC nomenclature — same category, different rating tables.
| Paramètres | 12 kV Class | 24 kV Class | 40.5 kV Class |
|---|---|---|---|
| Rated voltage (Ur) | 12 kV | 24 kV | 40.5 kV (36 kV IEC) |
| Lightning impulse withstand (Up) | 75 kV | 125 kV | 185 kV |
| Power-frequency withstand (Ud) | 28 kV | 50 kV | 95 kV |
| Typical rated normal current | 630–4,000 A | 630–2,500 A | 630–2,000 A |
| Typical short-time withstand (Ik) | 16–31.5 kA | 16–25 kA | 25–40 kA |
| Best fit | Industrial and commercial distribution | 20–24 kV utility networks, long feeders | Utility substations, 35 kV collection, heavy industry |
Exact insulation levels must be confirmed against the IEC 62271-200 rating tables and your utility’s network parameters — the values above are the levels most commonly specified for each class.
The 12 kV class is the workhorse of medium-voltage distribution and the most widely specified class worldwide. It serves 10–12 kV utility networks, factory primary distribution, commercial and infrastructure substations, and MV rooms in data centres and hospitals. A typical line-up combines incoming, metering, transformer-infeed and feeder panels, each with the withdrawable vacuum circuit breaker characteristic of metal-clad construction.
Our KYN28-12 armored withdrawable type AC metal-enclosed switchgear is the reference platform for this class: an IEC 62271-200 type-tested assembly with full compartmentalisation and a rackable VCB truck, available in ratings from 630 A to 3,150 A with short-time withstand up to 31.5 kA.

The 24 kV class exists for a simple reason: many utility networks — particularly in Europe, the Middle East, Australia and parts of Southeast Asia — distribute at 20–24 kV rather than 10–12 kV. Operating at a higher line voltage reduces current for the same power, which means lower losses and longer feeder reach.
Le 12kV vs 24kV switchgear decision is therefore usually settled by the utility supply, not by the designer. If the network’s highest voltage is above 12 kV, specifying a 12 kV class assembly is not permissible because the insulation coordination (125 kV BIL / 50 kV power-frequency for the 24 kV class) cannot be met. Conversely, if your network runs at 10–12 kV, a 24 kV panel is unnecessary cost and bulk. The same KYN28 platform is offered in the 24 kV version, so panel layouts and spare-part logistics stay consistent across both classes.
See the KYN28-24 metal-clad withdrawable type AC metal-enclosed switchgear for the 24 kV variant of this platform.

At 40.5 kV (the IEC 36 kV class), the application profile shifts toward utility substations that step down to the 10–12 kV distribution network, 35 kV collector systems in wind and solar plants, and heavy industry — steel, petrochemical and cement plants — where the plant infeed must match a 35 kV utility supply. Insulation requirements jump significantly (185 kV lightning impulse, 95 kV power-frequency), which is why 40.5 kV assemblies are physically larger, with longer phase clearances and a different cubicle architecture than 12/24 kV panels.
Le KYN61 40.5kV switchgear platform was developed for exactly this duty. Our KYN61-40.5 metalclad removable AC metal-enclosed switchgear carries the same withdrawable metal-clad principles into the 40.5 kV class, with rated currents up to 2,000 A and short-time withstand up to 40 kA for substation infeed duty.

Before requesting quotations, run your specification through the selection matrix below. It condenses the checks our application engineers perform when sizing a metal-clad line-up, and it works as a quick self-audit for EPC teams and consultants.
| Selection Factor | 12 kV Class | 24 kV Class | 40.5 kV Class |
|---|---|---|---|
| System highest voltage (Um) | ≤ 12 kV | 17.5–24 kV | 36–40.5 kV |
| Altitude & environment check | Above 1,000 m or C4/C5 pollution → insulation uprating | Same rule; verify creepage distances | Same rule; outdoor/kiosk versions need IP and climate checks |
| Fault level check | Match Ik and duration (1 s / 3 s / 4 s) to utility data | Same; confirm busbar and VCB ratings together | Sub-transmission faults are severe — confirm 25/31.5/40 kA with duration |
| Maintenance strategy | Withdrawable truck allows breaker service without busbar outage | Same principle | Same principle; check splicing and truck-handling clearances |
Then complete the five-point checklist:
Need Help Confirming Your Voltage Class?
Send us your single-line diagram or load data, and our engineers will verify the voltage class, insulation levels and fault ratings for your project — typically within one working day.
One question that follows voltage class selection is the breaker mounting arrangement. In a withdrawable metal enclosed switchgear assembly, the vacuum circuit breaker sits on a truck with primary disconnects and a secondary control plug, so it can be racked out for inspection or replacement while the rest of the line-up stays energised. Fixed construction, by contrast, has the breaker bolted into the cubicle — simpler and cheaper, but any breaker maintenance requires a full panel outage.
For metal-clad construction specifically, withdrawable is the norm, and both the KYN28 and KYN61 platforms follow this principle with mechanical interlocks that prevent racking the breaker under load or closing it in a test position. If your operation runs continuous processes — data centres, steel plants, petrochemical complexes — the withdrawable arrangement is usually worth the premium. You can review the full range of medium and high voltage switchgear cabinets to compare configurations across all three voltage classes.
Metal-clad switchgear is not the only answer at distribution level. For compact secondary substations, pad-mounted applications and ring/radial network points where a full line-up is more than the duty requires, a ring main unit (RMU) is often the more economical choice: a sealed, SF6-free or gas-insulated assembly combining load break switches, fuse protection and optionally a vacuum circuit breaker, usually in a fixed configuration.
A practical rule of thumb: use an RMU where the load is simple, switching is occasional and footprint matters; use metal-clad switchgear where fault levels are high, breaker maintenance is required, or the substation feeds critical processes. Our les unités principales en anneau (UPA) cover 12–36 kV in air-insulated, gas-insulated and solid-insulated designs for exactly these network positions.
Voltage class selection is only credible if the manufacturer can prove it. For any metal-clad assembly, request type test reports covering, as a minimum: dielectric tests (Up and Ud for your class), temperature-rise tests at rated current, short-circuit withstand tests at your Ik and duration, internal arc classification (IAC) tests, and mechanical endurance — with the circuit breakers themselves certified under IEC 62271-100.
Chuanli Electric manufactures the complete 12–40.5 kV range as an ISO 9001 certified plant and a long-term supplier to China State Grid projects, including the Three Gorges hydropower scheme and West–East Power Transmission corridors. Those references matter for one practical reason: type test certificates for each voltage class are held against the actual production platforms, not borrowed designs — which is what a procurement team should verify before shortlisting any supplier.
Four issues account for most voltage-class related rework we see in tenders:
Ready to Specify Your 12/24/40.5kV Line-Up?
Share your RFQ documents or single-line diagram and receive a tailored technical proposal with type test report extracts for the exact voltage class you need.
The difference is the rated voltage and the insulation system built around it. A 12 kV assembly is tested at 75 kV lightning impulse and 28 kV power-frequency, the 24 kV class at 125 kV / 50 kV, and the 40.5 kV class at 185 kV / 95 kV. Each class also differs in cabinet size, phase clearances and typical applications: 12 kV for standard distribution, 24 kV for 20–24 kV utility networks, and 40.5 kV for substations and heavy industry.
Match the switchgear rated voltage to the system highest voltage (Um) of your network. If your utility supplies at 10–12 kV, specify the 12 kV class; at 20–24 kV, the 24 kV class; at 35–36 kV, the 40.5 kV class. The rated voltage of the assembly must always be equal to or higher than Um — never lower.
They refer to the same application category but use different rating tables: 40.5 kV is the GB/T 3906 designation used in China, while 36 kV is the IEC designation. When comparing quotations, check the actual insulation levels — typically 185 kV lightning impulse and 95 kV power-frequency — rather than the label.
Metal-clad switchgear is a stricter subset of metal-enclosed switchgear. Under IEC 62271-200, metal-clad construction requires earthed metal barriers between all major compartments (busbar, breaker, cable, control) and a withdrawable circuit breaker. General metal-enclosed assemblies have a metallic enclosure but may use fixed devices and less segregation, which limits maintenance flexibility.
KYN28 and KYN61 are both withdrawable metal-clad platforms, but they serve different voltage classes: KYN28 covers the 12 kV and 24 kV classes with a compact cubicle, while KYN61 is the larger 40.5 kV (36 kV IEC) platform with longer clearances, higher impulse withstand and ratings up to 2,000 A / 40 kA.
Yes — an assembly rated for a higher voltage can be operated on a lower-voltage system, since the insulation is more than adequate. The trade-off is cost and size, because 24 kV cubicles are larger and more expensive than necessary for a 12 kV network. The reverse, however, is never acceptable: a 12 kV class assembly cannot be used on a 24 kV or 40.5 kV system.
Take the value from your utility’s fault study, which states both the short-circuit current and its duration. Commonly specified ratings are 20–31.5 kA for 12 kV distribution, 16–25 kA for 24 kV networks and 25–40 kA for 40.5 kV substations, with durations of 1 s, 3 s or 4 s. Always state current and duration together, e.g. 31.5 kA / 3 s, and ensure the busbar, VCB and earthing switch ratings are all coordinated to that value.