Vue d'ensemble
L'appareillage de commutation mobile blindé à fermeture métallique pour courant alternatif de type KYN61-40.5(Z) (ci-après dénommé "appareillage de commutation") convient au système électrique triphasé à courant alternatif de 50 Hz, aux centrales électriques, aux sous-stations et aux entreprises industrielles et minières de la salle de distribution pour accepter et distribuer l'énergie électrique, ainsi qu'au contrôle, à la protection et à la surveillance des circuits.
Ce produit est conforme aux normes : GB3906 "3~35kV AC metal enclosed switchgear", GB/T11022 "High voltage switchgear and control equipment standard common technical requirements", IEC60298 "rated voltage above 1kV and below 50kV AC metal enclosed switchgear and control equipment".
Signification du modèle
K |
Y |
N |
61 |
|
40.5 |
|
/ |
□ |
□ |
↓ |
↓ |
↓ |
↓ |
|
↓ |
↓ |
|
↓ |
↓ |
Metal
armoured
type |
Shifting
type |
Intérieur |
Conception
séquence
nombre |
|
Classé
tension
(kV) |
Type of
disjoncteur
Z:Vacuum
SF:6Sulfur
hexafluoride |
|
Classé
actuel
(A) |
Classé
court-circuit
Breaking
courant(kA) |
Conditions d'utilisation
- Température de l'air ambiant : température maximale +40℃ , température minimale -15℃ ;
• Altitude: ≤ 2000m;
• Surrounding relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
• Ambient air: not suitable for places with corrosion, serious pollution, flammable gas and violent vibration;
• If an earthquake occurs, the intensity of the earthquake cannot exceed 8 degrees.
Caractéristiques structurelles
Switchgear structure GB3906-2006 and IEC298 armored metal closed switchgear standard design, the whole by the cabinet and withdrawable part (handcar) of two levels. The structure of the cabinet is assembled, and the part of the switchgear body is separated into the circuit breaker room, the main bus room, the cable room and the relay instrument room with a metal partition. The protection level of the enclosure reaches IP3X, the protection level of the compartments is IP2X, and all metal structural parts are reliably grounded, and the compartments of the main circuit system have independent exhaust pressure relief channels.
According to the use of the handcart can be divided into circuit breaker handcart, voltage transformer handcart, measuring handcart, isolation handcart,etc., all kinds of handcart outline size is the same, the same purpose of the handcart has good interchangeability; The cart has a test/isolation position and a working position in the cabinet, and each position is equipped with an interlock device to ensure that the cart cannot move freely when it is in the above two positions.
KYN61-40.5 Appareils de commutation amovibles à enveloppe métallique pour courant alternatif
Paramètres |
Unité |
Valeur |
Tension nominale |
KV |
40.5 |
Rated Current |
Rated current of main bus bar |
A |
1250,1600,2000,(2500) |
Rated current of matched VCB |
A |
1250,1600,2000,(2500) |
Rated Insulation Level |
1 min fréquence d'alimentation tension de résistance |
KV |
95 |
Tension de résistance aux chocs de foudre |
KV |
185 |
Power frequency withstands voltage of
auxiliary circuit and control circuit |
V/1min |
2000 |
Fréquence nominale |
Hz |
50 |
Courant nominal de rupture en court-circuit |
KA |
202531.5 |
Courant nominal de courte durée |
KA/4s |
202531.5 |
Rated withstands current(peak) |
KA |
50,63,80 |
Rated voltage of control circuit |
V |
DC:110,220
AC:110,220 |