Visión general
KYN61-40.5(Z) type armored movable AC metal closed switchgear (hereinafter referred to as “switchgear”) It is suitable for three-phase AC 50Hz power system, for power plants, substations and industrial and mining enterprises of the distribution room to accept and distribute electrical energy, and the circuit control, protection and monitoring.
This product conforms to the standards: GB3906 “3~35kV AC metal enclosed switchgear”, GB/T11022 “High voltage switchgear and control equipment standard common technical requirements”, IEC60298 “rated voltage above 1kV and below 50kV AC metal enclosed switchgear and control equipment”.
Modelo Significado
K |
Y |
N |
61 |
|
40.5 |
|
/ |
□ |
□ |
↓ |
↓ |
↓ |
↓ |
|
↓ |
↓ |
|
↓ |
↓ |
Metal
armoured
type |
Shifting
type |
Interior |
Diseño
secuencia
número |
|
Rated
tensión
(kV) |
Type of
circuit breaker
Z:Vacuum
SF:6Sulfur
hexafluoruro |
|
Rated
actual
(A) |
Rated
cortocircuito
Breaking
corriente(kA) |
Condiciones de uso
• Ambient air temperature: maximum temperature +40℃ , minimum temperature -15℃ ;
• Altitude: ≤ 2000m;
• Surrounding relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
• Ambient air: not suitable for places with corrosion, serious pollution, flammable gas and violent vibration;
• If an earthquake occurs, the intensity of the earthquake cannot exceed 8 degrees.
Structural Characteristics
Switchgear structure GB3906-2006 and IEC298 armored metal closed switchgear standard design, the whole by the cabinet and withdrawable part (handcar) of two levels. The structure of the cabinet is assembled, and the part of the switchgear body is separated into the circuit breaker room, the main bus room, the cable room and the relay instrument room with a metal partition. The protection level of the enclosure reaches IP3X, the protection level of the compartments is IP2X, and all metal structural parts are reliably grounded, and the compartments of the main circuit system have independent exhaust pressure relief channels.
According to the use of the handcart can be divided into circuit breaker handcart, voltage transformer handcart, measuring handcart, isolation handcart,etc., all kinds of handcart outline size is the same, the same purpose of the handcart has good interchangeability; The cart has a test/isolation position and a working position in the cabinet, and each position is equipped with an interlock device to ensure that the cart cannot move freely when it is in the above two positions.
KYN61-40.5 Celdas con envolvente metálica de CA extraíble Metalclad
Parameter |
Unidad |
Value |
Rated Voltage |
KV |
40.5 |
Rated Current |
Rated current of main bus bar |
A |
1250,1600,2000,(2500) |
Rated current of matched VCB |
A |
1250,1600,2000,(2500) |
Rated Insulation Level |
1 min power frequency withstand voltage |
KV |
95 |
Tensión soportada al impulso del rayo |
KV |
185 |
Power frequency withstands voltage of
auxiliary circuit and control circuit |
V/1min |
2000 |
Frecuencia nominal |
Hz |
50 |
Corriente asignada de corte en cortocircuito |
KA |
202531.5 |
Corriente nominal de corta duración |
KA/4s |
202531.5 |
Rated withstands current(peak) |
KA |
50,63,80 |
Rated voltage of control circuit |
V |
DC:110,220
AC:110,220 |