Vue d'ensemble
When your turnkey project requires a low-profile, highly secure outdoor power solution, our three-phase pad-mounted transformer delivers industrial-grade performance directly to your site. Engineered specifically for underground distribution systems, Clelek provides you with highly customizable units ranging from 45 kVA to 5000 kVA, with primary voltages up to 34.5 kV. As a dedicated pad-mounted transformer manufacturer with 20 years of North American market experience, we ensure every liquid-filled unit streamlines your commercial power distribution network with maximum efficiency and zero safety compromise.
Caractéristiques principales
● Construction robuste : Boîtiers en acier de fort calibre avec fi nition enduite de poudre cuite au four pour l'inviolabilité et la durabilité à l'épreuve des intempéries.
● Des configurations flexibles : Disponibles dans des conceptions à front vivant et à front mort, prenant en charge les applications radiales ou à alimentation en boucle.
● Technologie Eco-Safe : Rempli de fluide diélectrique biodégradable durable pour une protection supérieure du fi l et une durée de vie prolongée.
Applications primaires
● Services publics : Solutions de transformateurs abaisseurs
● Exploitation minière de bitcoins : Transformateurs côté charge spécialisés de 415 V (configuration en Y).
● Fermes solaires : Systèmes de transformateurs élévateurs
● Industriel : Convient aux environnements exigeants, y compris les emplacements dangereux.
Avantages techniques
● 20 ans d'expérience du marché nord-américain
● Gamme complète de transformateurs de distribution sur socle alimentés en liquide.
● Conformité aux normes opérationnelles nord-américaines rigoureuses.
● Solutions d'ingénierie personnalisées disponibles
Couverture des services
Fournir des solutions professionnelles de transformation pour les services publics, les énergies renouvelables et les secteurs industriels dans toute l'Amérique du Nord.
Types de fluides isolants
Un transformateur à bain d'huile est généralement utilisé à l'extérieur en raison des préoccupations liées aux déversements d'huile ou aux fuites si l'huile atteint son point d'ébullition. Récemment, de nouveaux liquides isolants (par exemple, le liquide de silicone, FR3) ont été mis au point avec une température de point de cendre plus élevée que l'huile minérale, et les transformateurs équipés de ces liquides peuvent être utilisés à l'intérieur. Cependant, il est important de noter que ces transformateurs à immersion liquide moins inflammables ont des coûts initiaux plus élevés que leurs homologues de type sec, ce qui empêche leur adoption généralisée sur le marché.
Pour les applications de transformateurs, le silicone est idéal en raison de sa stabilité à la chaleur, de sa compatibilité avec les matériaux, de sa faible inflammabilité et de sa faible toxicité. Le point de fusion élevé de 340 oC de la silicone en fait un fluide moins inflammable, répertorié par l'UL et approuvé par les mutuelles d'usine pour les applications intérieures et extérieures. Il est idéal dans les endroits où les risques d'incendie sont présents et où des systèmes spéciaux de suppression des incendies sont en place.
Le fluide diélectrique FR3 est entièrement biodégradable et respectueux de l'environnement. Il convient à une utilisation en intérieur et dans les zones à forte sensibilité environnementale où tout fl uide isolant renversé pourrait nécessiter un nettoyage approfondi.
Dimensions minimales et spécifiques
Il existe deux configurations pour la conception de la zone morte : les dimensions minimales et les dimensions spécifiques. Les dimensions minimales couvrent l'espacement minimal entre les bagues, la hauteur des bagues et la profondeur des compartiments. En revanche, les dimensions spécifiques couvrent des dimensions autres que les dimensions minimales, tout en tenant compte des installations, de l'entretien et de la facilité de raccordement.
Caractéristiques standard d'un transformateur sur socle

| Numéro de série |
Nom |
| 1 |
Crochets de levage |
| 2 |
Compartiment à bornes avec seuil avant amovible |
| 3 |
Portes d'armoire à charnières, rabattables |
| 4 |
Poignée de cadenas à tête pentagonale emboîtée |
| 5 |
Patins de mise à la terre (non illustrés) |
| 6 |
Barrières de compartiment |
| 7 |
Plaque signalétique |
| 8 |
Dispositif de décompression |
| 9 |
Changeur de robinet |
| 10 |
Vanne de vidange |
| 11 |
Courroie de masse amovible |
| 12 |
Puits à douilles (pour la conception de l'avant mort) |
| 13 |
Douilles biseautées (pour la conception du front de taille) |
| 14 |
Supports de stationnement |
| 15 |
Cosses à broches |
| 16 |
Interrupteur de rupture de charge |
| 17 |
Fusible Bay-O-Net |
| 18 |
Jauge de niveau de liquide |
S22M Oil To Level 1 Efficacité énergétique
| Capacité nominale
(kVA) |
Tension primaire
(V) |
Tension secondaire
(V) |
Gamme de prises HV |
Impédance
Pourcentage(%Z) |
Tension nominale de la ligne :
Standard BIL(KV) |
Certifications |
| 45 |
440V-35,000V |
208/120Y-34,500V |
2×±2,5% |
2.70-5.75 |
1,2KV:30KV
2,5KV:45KV
5.0kV:60KV
8,7KV:75KV
15KV:95KV
25kV:125/150KV
34,5kV:150KV |
UL/C-UL |
| 75 |
2×±2,5% |
2.70-5.75 |
UL/C-UL |
| 112.5 |
2×±2,5% |
3.10-5.75 |
UL/C-UL |
| 150 |
2×±2,5% |
3.10-5.75 |
UL/C-UL |
| 225-300 |
2×±2,5% |
3.10-5.75 |
UL/C-UL |
| 500 |
2×±2,5% |
4.35-5.75 |
UL/C-UL |
| 750-10,000 |
2×±2,5% |
5.75-6.50 |
UL/C-UL |
Dimensions de l'agencement

Transformateur sur socle - Dimensions en pouces (mm)
| kVA |
A |
B |
C |
D |
E |
F |
I |
Gallons |
Approximation
Poids |
DOE 2016
Efficacité |
| 45 |
50 |
68 |
39 |
42 |
26 |
68 |
20 |
115 |
2150 |
0.9892 |
| 75 |
50 |
68 |
39 |
42 |
26 |
68 |
20 |
125 |
2350 |
0.9903 |
| 112.5 |
50 |
68 |
39 |
42 |
26 |
68 |
20 |
135 |
2600 |
0.9911 |
| 150 |
50 |
68 |
49 |
42 |
26 |
68 |
20 |
150 |
2900 |
0.9916 |
| 225 |
50 |
72 |
53 |
42 |
30 |
72 |
20 |
170 |
3400 |
0.9923 |
| 300 |
50 |
72 |
55 |
42 |
30 |
72 |
20 |
190 |
3950 |
0.9927 |
| 500 |
50 |
72 |
61 |
42 |
30 |
72 |
20 |
240 |
5300 |
0.9935 |
| 750 |
64 |
72 |
63 |
42 |
30 |
72 |
20 |
300 |
7150 |
0.994 |
| 1000 |
64 |
72 |
64 |
42 |
30 |
72 |
20 |
350 |
8950 |
0.9943 |
| 1500 |
73 |
89 |
71 |
42 |
30 |
72 |
24 |
400 |
11450 |
0.9948 |
| 2000 |
73 |
101 |
75 |
42 |
30 |
72 |
24 |
525 |
13800 |
0.9951 |
| 2500 |
73 |
101 |
99 |
42 |
30 |
72 |
24 |
600 |
16750 |
0.9953 |
Note : Les dimensions de référence dans ce tableau couvrent les éléments suivants : configurations frontales et frontales, alimentation en boucle et alimentation radiale, unités remplies d'huile minérale et de FR3.
Variations dimensionnelles
Variations de hauteur
1. Ajoutez 9,00 pouces (228,6 mm) à la hauteur lorsque vous utilisez des fusibles à baïonnette pour tous les kVA.
2. Le fluide d'éther naturel, moins inflammable, nécessite des réservoirs plus profonds pour certaines catégories de transformateurs.
3. Ajouter 2,00 pouces (50,8 mm) à la profondeur des calibres kVA 75-1500. Ajouter 8,00 pouces (203,2 mm) à la profondeur des valeurs kVA 2000 et 2500.
Integrating Pad-Mounted Transformers Into Your Distribution Substation
Building a resilient medium-voltage network requires seamless synchronization between your outdoor transformers and indoor switchgear control rooms:
FAQ
1: What is the capacity range and efficiency standard of Clelek’s three-phase pad-mounted transformers?
Our three-phase pad-mounted transformers cover a wide rated capacity range from 45 kVA up to 2500 kVA (and custom solutions up to 5000 kVA). Every unit in this product line is meticulously engineered to meet DOE 2016 energy efficiency standards, ensuring minimal core losses and lower long-term operational costs for your utility network.
2: Can I choose eco-friendly insulating fluids for indoor or environmentally sensitive installations?
Yes, you can. While standard mineral oil is highly cost-effective for typical outdoor commercial power distribution, we offer premium FR3 dielectric fluid and silicone fluid options. With high fire points (FR3 and silicone reach over 300°C and 340°C respectively), these less-flammable, fully biodegradable liquids are UL Listed and Factory Mutual approved, making them ideal for your indoor layouts or zero-tolerance eco-sensitive areas.
3: What is the structural difference between minimum dimensions and specific dimensions in your deadfront design?
When you specify a deadfront design for your project, we offer two layout configurations. Minimum dimensions strictly cover the mandatory clearance requirements, including standard bushing spacing, bushing height, and primary compartment depth. In contrast, specific dimensions extend beyond the bare minimums to give your field technicians extra spatial clearance for easier cable connection, safer routine maintenance, and smoother tool maneuvering.
4: Do your transformers support customized configurations for Bitcoin mining and renewable energy?
Absolutely. We possess extensive experience tailoring units for demanding environments. For crypto mining infrastructure, we provide specialized 415V (Y-configuration) load-side transformers optimized for high harmonic loads. For solar farms and wind plants, we engineer heavy-duty step-up transformer systems designed to withstand the cyclic power fluctuations typical of renewable energy generation.
5: What technical details should I provide to get a wholesale B2B quote from Clelek?
To ensure our engineering team delivers an accurate quotation and lead time within 24 hours, please submit your required kVA rating (e.g., 500 kVA, 750 kVA), primary voltage (up to 34.5 kV), secondary voltage (e.g., 208Y/120V, 480Y/277V), feed layout (Loop feed or Radial feed), and front configuration (Dead-front or Live-front). Contact our North American support desk to initiate your custom engineering request.