Overview
FN7-12DR type AC high-voltage load switch is a new type of gas production type indoor high-voltage load switch, which is suitable for the three-phase AC power system with AC 50Hz and rated voltage 12KV, and is used for breaking load current and closing short-circuit current.
Main Technical Parameters
| Rated voltage(KV RMS) |
12 |
| Insulation level |
Power frequency 50Hz withstand voltage 1min(KV.Effective value) |
Phase to phase 42 |
Isolation fracture 48 |
| Lightning impulse withstand voltage(KV.Peak) |
Phase to phase 75 |
Isolation fracture 85 |
| Rated current (A) |
400 |
630 |
| Rated thermal stable current (KV.Effective value 4S) |
12.5 |
20 |
| Rated dynamic stable current(KV.Value) |
31.5 |
50 |
| Rated short circuit closing current(KA.Peak) |
31.5 |
50 |
Installation And Use
Normal use conditions:
Ambient air temperature: Upper limit: +40℃ ; Lower limit: 10℃ in general area, -25℃ in high cold area
Altitude: The sea level is 1000m and below
Relative humidity: daily average less than 95%, monthly average less than 90%
The surrounding air should not be significantly polluted by corrosive or flammable gases and water vapor
No frequent violent vibration
Main Specification
| Name |
Model |
DS |
DK |
L |
R |
RA |
F |
| The ground switch is at the incoming end |
The ground switch is at the outgoing end |
Interlocking device |
Fuse |
Knock out fuse |
Electric brake opening device |
| Load switch |
FN7-12 |
– |
|
|
|
|
– |
| FN7-12DSL |
△ |
– |
△ |
– |
|
– |
| FN7-12DXL |
– |
△ |
△ |
|
|
|
| FN7-12R |
– |
– |
– |
△ |
– |
– |
| FN7-12DSLR |
△ |
– |
△ |
△ |
– |
– |
| FN7-12DXLR |
– |
△ |
△ |
△ |
|
– |
| FN7-12RAF |
– |
– |
– |
– |
△ |
△ |
| FN7-2DSLRAF |
△ |
– |
|
– |
△ |
△ |
| FN7-2DXLRAF |
|
△ |
|
– |
△ |
△ |
Dimensions And Mounting Dimensions (mm)