Visão geral
As a leading high-voltage electrical equipment supplier, Chuanli Electric delivers the 10kV/20kV/24kV SC(B)13, SC(B)14, and SC(B)18 epoxy cast resin dry-type transformers. Engineered for high-density urban power grids, data centers, and heavy industrial facilities, these units serve as the ideal eco-friendly alternative to traditional oil-immersed distribution transformers. Whether you are an EPC contractor or an industrial utility manager, our cast resin transformers guarantee peak operational reliability, meeting strict international IEC standards for high-voltage distribution networks.
Significado do modelo
| S | C | (B) | □ | – | □ | / | □ |
| ↓ | ↓ | ↓ | ↓ | | ↓ | | ↓ |
| Trifásico | Isolamento de resina | Folha de baixa tensão
enrolamento | Nível de desempenho
Nome do código | | Capacidade nominal
(KVA) | | Grau de tensão
(KV) |
Características do produto
Os transformadores de potência de 10/20/24kV SC(B)13/14/18 produzidos por nossa fábrica são transformadores do tipo seco com bobina enrolada em resina de baixo ruído e baixa perda com certificado de tipo de produto. Devido ao design avançado, aos materiais de alta qualidade, à formulação científica, ao processo rigoroso e ao alto padrão de testes, os produtos têm as seguintes características:
O enrolamento de alta tensão do fio de cobre, o enrolamento de baixa tensão do fio de cobre ou da folha de cobre, o tapete de fibra de vidro é preenchido com embalagem, embalagem a vácuo do epóxi usado sem fundição, cura para formar um conjunto cilíndrico sólido, alta resistência mecânica, descarga parcial pequena e alta confiabilidade.
Antichamas e antiexplosão não poluem o meio ambiente. A bobina de enrolamento de fibra de vidro tem propriedades autoextinguíveis e não produz arco elétrico em caso de curto-circuito, não produz gases tóxicos ou nocivos em condições de alta temperatura.
A bobina não absorve umidade, os grampos do núcleo têm uma camada especial de proteção contra corrosão, umidade relativa de 100% e outros ambientes adversos. O acionamento interrompido não precisa remover o tratamento de maré.
Resistente a curto-circuito e com alto nível de impulso de voo.
A resina dentro e fora da bobina é fina, a dispersão de calor é boa. O ar de resfriamento é usado como ar frio na natureza (AN). Para qualquer grau de proteção do transformador, equipe-o com o sistema de resfriamento a ar (AF), a fim de melhorar a capacidade de sobrecarga de curto prazo e garantir uma operação segura.
Menor consumo, economia de energia. Funcionando com economia, pode ser livre de manutenção.
Volume pequeno, peso leve, área pequena, custos de instalação mais baixos, sem necessidade de considerar o tanque de óleo, proteção contra incêndio e energia de backup, UPS em stand-by.
Como não há perigo de incêndio e explosão, a instalação no centro de carga pode ser distribuída e totalmente próxima ao ponto de energia, reduzindo assim o baixo custo da linha e economizando os caros custos das instalações.
SC (B) 13 Transformador do tipo seco
| Tipo | Classificado Capacidade (KVA) | Combinações de tensão e faixa de taps | Conexão símbolo do grupo | Sem carga perda (W) | Perda de carga 75℃ (W) | Sem carga atual (%) | Curto-circuito impedância (%) |
Alta pressão (kV) | Alta pressão Faixa de tap (%) | Baixa pressão (kV) |
| SC(B)13-30 | 30 | 24
20
10
6.3
6 | ±5%
±2×2.5
/
×2.5
+3
-1 | 0.4 | Yyn0
/
Dyn11 | 135 | 640 | 2.0 | 4.0 |
| SC(B)13-50 | 50 | 195 | 900 | 2.0 |
| SC(B)13-80 | 80 | 265 | 1240 | 1.5 |
| SC(B)13-100 | 100 | 290 | 1410 | 1.5 |
| SC(B)13-125 | 125 | 340 | 1660 | 1.3 |
| SC(B)13-160 | 160 | 385 | 1910 | 1.3 |
| SC(B)13-200 | 200 | 445 | 2270 | 1.1 |
| SC(B)13-250 | 250 | 515 | 2480 | 1.1 |
| SC(B)13-315 | 315 | 635 | 3120 | 1.0 |
| SC(B)13-400 | 400 | 705 | 3590 | 1.0 |
| SC(B)13-500 | 500 | 835 | 4390 | 1.0 |
| SC(B)13-630 | 630 | 965 | 5290 | 0.85 |
| SC(B)13-630 | 630 | 935 | 5360 | 0.85 | 6.0 |
| SC(B)13-800 | 800 | 1090 | 6260 | 0.85 |
| SC(B)13-1000 | 1000 | 1270 | 7310 | 0.85 |
| SC(B)13-1250 | 1250 | 1500 | 8720 | 0.85 |
| SC(B)13-1600 | 1600 | 1760 | 10500 | 0.85 |
| SC(B)13-2000 | 2000 | 2190 | 13000 | 0.7 |
| SC(B)13-2500 | 2500 | 2590 | 15400 | 0.7 |
SCB14 Dry Change Nível 2 de eficiência energética
| Capacidade nominal (kVA) | Perda sem carga (W | Perda de carga (W) | Corrente sem carga (%) | Dimensões (mm) |
| 30 | 130 | 640 | 2.0% | 700*360*675 |
| 50 | 180 | 900 | 2.0% | 770*460*710 |
| 80 | 250 | 1240 | 1.5% | 770*460*770 |
| 100 | 270 | 1415 | 1.3% | 790*460*730 |
| 125 | 320 | 1665 | 1.3% | 870*460*845 |
| 160 | 365 | 1915 | 1.1% | 860*460*805 |
| 200 | 420 | 2275 | 1.1% | 940*920*806 |
| 250 | 490 | 2485 | 1.0% | 960*920*906 |
| 315 | 600 | 3125 | 1.0% | 980*970*906 |
| 400 | 665 | 3590 | 1.0% | 1010*970*936 |
| 500 | 790 | 4390 | 1.0% | 1030*970*956 |
| 630 | 885 | 5360 | 0.9% | 1220*1120*906 |
| 800 | 1035 | 6265 | 0.9% | 1270*1170*946 |
| 1000 | 1205 | 7315 | 0.9% | 1300*117*1016 |
| 1250 | 1420 | 8720 | 0.9% | 1370*1220*1051 |
| 1600 | 1665 | 10555 | 0.9% | 1450*1270*1161 |
| 2000 | 2075 | 13005 | 0.7% | 1470*1270*1295 |
| 2500 | 2450 | 15445 | 0.7% | 1450*1320*1336 |
SCB18 Dry Change Nível 1 de eficiência energética
| Capacidade nominal (kVA) | Perda sem carga (W) | Perda de carga (W) | Corrente sem carga (%) | Dimensões (mm) |
| 30 | 130 | 640 | 2.0% | 700*360*675 |
| 50 | 185 | 900 | 2.0% | 770*460*710 |
| 80 | 250 | 1240 | 1.5% | 770*460*770 |
| 100 | 270 | 1415 | 1.3% | 790*460*730 |
| 125 | 320 | 1665 | 1.3% | 870*460*845 |
| 160 | 365 | 1915 | 1.1% | 860*460*805 |
| 200 | 420 | 2275 | 1.1% | 940*920*806 |
| 250 | 490 | 2485 | 1.0% | 960*920*856 |
| 315 | 510 | 3125 | 1.0% | 980*970*906 |
| 400 | 570 | 3590 | 1.0% | 1010*970*936 |
| 500 | 670 | 4390 | 1.0% | 1030*970*956 |
| 630 | 750 | 5365 | 0.9% | 1220*1120*906 |
| 800 | 875 | 6265 | 0.9% | 1270*1170*946 |
| 1000 | 1020 | 7315 | 0.9% | 1300*1170*1016 |
| 1250 | 1205 | 8720 | 0.9% | 1370*1220*1051 |
| 1600 | 1415 | 10555 | 0.9% | 1450*1270*1161 |
| 2000 | 1760 | 13005 | 0.7% | 1475*1270*1295 |
| 2500 | 2080 | 15445 | 0.7% | 1450*1320*1356 |
Complete B2B Power Distribution Solutions
To ensure grid stability and compliance with global energy regulations, choosing between Tier 1 and Tier 2 energy efficiency is critical. For instance, our SCB18 series delivers Tier 1 eco-design efficiency, significantly lowering long-term operational costs in large-scale solar projects and infrastructure.
When designing a turnkey distribution substation, a dry-type transformer must operate seamlessly with upstream and downstream high-voltage protection devices:
1. Upstream Protection: Learn more about selecting the right grid breakers in our technical guide on Componentes principais dentro de um gabinete de painel.
2. Photovoltaic & Renewable Integration: If you are engineering for clean energy plants, discover How to Adapt Prefabricated Switchgear to the High-Voltage Distribution Requirements of 10kv Photovoltaic Power Plants.
3. System Maintenance: Avoid costly downtime by reviewing our professional guide on Power Transformer Repair: How to Identify Repairable vs Non-Repairable Faults.
FAQ about SC(B) 13/14/18 Dry-Type Transformers
1. What is the main difference between SCB13, SCB14, and SCB18 dry transformers?
The primary difference lies in their energy efficiency levels and core loss reduction. Our SCB18 series meets Level 1 energy efficiency standards, reducing no-load losses by up to 20-25% compared to the SCB13, which translates to massive long-term operational savings for your project.
2. Can your resin-insulated dry transformers operate in 100% humidity?
Yes, absolutely. Because our copper/foil windings are completely encapsulated in vacuum-cast epoxy resin, the coils do not absorb moisture. You can safely deploy them in 100% relative humidity and harsh environments without any pre-drying or “tide treatment” after idle periods.
3. Why should I choose a cast resin transformer over an oil-immersed transformer?
Cast resin transformers offer superior fire and explosion safety (self-extinguishing glass fiber insulation), making them ideal for high-density indoor spaces like subways, hospitals, and commercial centers. Additionally, you eliminate oil leakage risks, rendering them virtually maintenance-free.
4. What cooling options are available for your power transformers?
We provide two operational modes: Natural Air Cooling (AN) for standard, continuous load operations, and Forced Air Cooling (AF). With our integrated AF cooling system, you can increase the short-term overload capacity of your transformer by up to 40-50% for peak safety.
5. Do you provide custom voltage combinations and tap ranges?
Yes, we design for your specific grid matrix. Our standard line supports high voltage ratings of 6.3kV, 10kV, 20kV, and 24kV with tap ranges of ±5% or ±2×2.5%, stepping down to a low voltage of 0.4kV with standard Dyn11 or Yyn0 connection groups.