Visión general
As a leading high-voltage electrical equipment supplier, Chuanli Electric delivers the 10kV/20kV/24kV SC(B)13, SC(B)14, and SC(B)18 epoxy cast resin dry-type transformers. Engineered for high-density urban power grids, data centers, and heavy industrial facilities, these units serve as the ideal eco-friendly alternative to traditional oil-immersed distribution transformers. Whether you are an EPC contractor or an industrial utility manager, our cast resin transformers guarantee peak operational reliability, meeting strict international IEC standards for high-voltage distribution networks.
Modelo Significado
| S | C | (B) | □ | – | □ | / | □ |
| ↓ | ↓ | ↓ | ↓ | | ↓ | | ↓ |
| Trifásico | Aislamiento de resina | Lámina de baja tensión
bobinado | Nivel de rendimiento
Nombre en clave | | Capacidad nominal
(KVA) | | Grado de tensión
(KV) |
Características del producto
Los transformadores de potencia 10/20/24kV SC(B)13/14/18 producidos por nuestra fábrica son transformadores de tipo seco con bobina bobinada de resina de bajo ruido y bajas pérdidas con certificado de tipo de producto. Debido al diseño avanzado, materiales de alta calidad, formulación científica, proceso estricto y alto estándar de pruebas, los productos tienen las siguientes características:
El bobinado de alta tensión de alambre de cobre, bobinado de baja tensión de la herida de alambre de cobre o lámina de cobre, estera de fibra de vidrio está lleno de envoltura, envasado al vacío del epoxi utilizado sin fundición, curado para formar un sólido cilíndrico en general, de alta resistencia mecánica, descarga parcial de pequeñas, de alta fiabilidad.
Antiflaming. antiexplosión no contaminará el medio ambiente. Bobina de fibra de vidrio con propiedades autoextinguibles. y no produce arco eléctrico en caso de cortocircuito, no produce gases tóxicos o nocivos en condiciones de alta temperatura.
La bobina no absorbe la humedad, abrazaderas de núcleo tienen una capa de protección contra la corrosión speaal, 100% humedad relativa y otros ambientes ásperos. Interrumpir la conducción no es necesario quitar el tratamiento de marea.
Resistente a cortocircuitos y alto nivel de impulso luminoso.
La resina dentro y fuera de la bobina es delgada, la dispersión del calor es buena. El aire de refrigeración se utiliza aire frío en la naturaleza (AN). Para cualquier grado de transformador de protección, equipar con sistema de refrigeración por aire (AF), con el fin de mejorar la capacidad de sobrecarga de corto plazo, y garantizar un funcionamiento seguro.
Menor consumo, ahorro de energía. Funcionamiento para un ahorro, puede ser libre de mantenimiento.
Pequeño volumen, peso ligero, área pequeña, menores costes de instalación, sin necesidad de considerar el depósito de aceite, protección contra la rotura y alimentación de reserva, SAI de reserva.
Debido a que no había peligro de incendio y explosión, instalado en el centro de carga puede ser distribuido y totalmente cerca de la toma de corriente, por lo tanto reduang la línea de bajo costo y ahorrar los costosos costos de las instalaciones.
SC (B) 13 Transformador seco
| Tipo | Rated Capacidad (KVA) | Combinaciones de tensiones y rango de tomas | Conexión símbolo de grupo | Sin carga pérdida (W) | Pérdida de carga 75℃ (W) | Sin carga actual (%) | Cortocircuito impedancia (%) |
Alta presión (kV) | Alta presión rango de toma(%) | Baja presión (kV) |
| SC(B)13-30 | 30 | 24
20
10
6.3
6 | ±5%
±2×2.5
/
×2.5
+3
-1 | 0.4 | Yyn0
/
Din11 | 135 | 640 | 2.0 | 4.0 |
| SC(B)13-50 | 50 | 195 | 900 | 2.0 |
| SC(B)13-80 | 80 | 265 | 1240 | 1.5 |
| SC(B)13-100 | 100 | 290 | 1410 | 1.5 |
| SC(B)13-125 | 125 | 340 | 1660 | 1.3 |
| SC(B)13-160 | 160 | 385 | 1910 | 1.3 |
| SC(B)13-200 | 200 | 445 | 2270 | 1.1 |
| SC(B)13-250 | 250 | 515 | 2480 | 1.1 |
| SC(B)13-315 | 315 | 635 | 3120 | 1.0 |
| SC(B)13-400 | 400 | 705 | 3590 | 1.0 |
| SC(B)13-500 | 500 | 835 | 4390 | 1.0 |
| SC(B)13-630 | 630 | 965 | 5290 | 0.85 |
| SC(B)13-630 | 630 | 935 | 5360 | 0.85 | 6.0 |
| SC(B)13-800 | 800 | 1090 | 6260 | 0.85 |
| SC(B)13-1000 | 1000 | 1270 | 7310 | 0.85 |
| SC(B)13-1250 | 1250 | 1500 | 8720 | 0.85 |
| SC(B)13-1600 | 1600 | 1760 | 10500 | 0.85 |
| SC(B)13-2000 | 2000 | 2190 | 13000 | 0.7 |
| SC(B)13-2500 | 2500 | 2590 | 15400 | 0.7 |
SCB14 Cambio en seco Nivel 2 Eficiencia energética
| Capacidad nominal (kVA) | Pérdida en vacío (W | Pérdida de carga (W) | Corriente en vacío (%) | Dimensiones (mm) |
| 30 | 130 | 640 | 2.0% | 700*360*675 |
| 50 | 180 | 900 | 2.0% | 770*460*710 |
| 80 | 250 | 1240 | 1.5% | 770*460*770 |
| 100 | 270 | 1415 | 1.3% | 790*460*730 |
| 125 | 320 | 1665 | 1.3% | 870*460*845 |
| 160 | 365 | 1915 | 1.1% | 860*460*805 |
| 200 | 420 | 2275 | 1.1% | 940*920*806 |
| 250 | 490 | 2485 | 1.0% | 960*920*906 |
| 315 | 600 | 3125 | 1.0% | 980*970*906 |
| 400 | 665 | 3590 | 1.0% | 1010*970*936 |
| 500 | 790 | 4390 | 1.0% | 1030*970*956 |
| 630 | 885 | 5360 | 0.9% | 1220*1120*906 |
| 800 | 1035 | 6265 | 0.9% | 1270*1170*946 |
| 1000 | 1205 | 7315 | 0.9% | 1300*117*1016 |
| 1250 | 1420 | 8720 | 0.9% | 1370*1220*1051 |
| 1600 | 1665 | 10555 | 0.9% | 1450*1270*1161 |
| 2000 | 2075 | 13005 | 0.7% | 1470*1270*1295 |
| 2500 | 2450 | 15445 | 0.7% | 1450*1320*1336 |
SCB18 Cambio en seco Nivel 1 Eficiencia energética
| Capacidad nominal (kVA) | Pérdida en vacío (W) | Pérdida de carga (W) | Corriente en vacío (%) | Dimensiones (mm) |
| 30 | 130 | 640 | 2.0% | 700*360*675 |
| 50 | 185 | 900 | 2.0% | 770*460*710 |
| 80 | 250 | 1240 | 1.5% | 770*460*770 |
| 100 | 270 | 1415 | 1.3% | 790*460*730 |
| 125 | 320 | 1665 | 1.3% | 870*460*845 |
| 160 | 365 | 1915 | 1.1% | 860*460*805 |
| 200 | 420 | 2275 | 1.1% | 940*920*806 |
| 250 | 490 | 2485 | 1.0% | 960*920*856 |
| 315 | 510 | 3125 | 1.0% | 980*970*906 |
| 400 | 570 | 3590 | 1.0% | 1010*970*936 |
| 500 | 670 | 4390 | 1.0% | 1030*970*956 |
| 630 | 750 | 5365 | 0.9% | 1220*1120*906 |
| 800 | 875 | 6265 | 0.9% | 1270*1170*946 |
| 1000 | 1020 | 7315 | 0.9% | 1300*1170*1016 |
| 1250 | 1205 | 8720 | 0.9% | 1370*1220*1051 |
| 1600 | 1415 | 10555 | 0.9% | 1450*1270*1161 |
| 2000 | 1760 | 13005 | 0.7% | 1475*1270*1295 |
| 2500 | 2080 | 15445 | 0.7% | 1450*1320*1356 |
Complete B2B Power Distribution Solutions
To ensure grid stability and compliance with global energy regulations, choosing between Tier 1 and Tier 2 energy efficiency is critical. For instance, our SCB18 series delivers Tier 1 eco-design efficiency, significantly lowering long-term operational costs in large-scale solar projects and infrastructure.
When designing a turnkey distribution substation, a dry-type transformer must operate seamlessly with upstream and downstream high-voltage protection devices:
1. Upstream Protection: Learn more about selecting the right grid breakers in our technical guide on Componentes clave de un armario eléctrico.
2. Photovoltaic & Renewable Integration: If you are engineering for clean energy plants, discover How to Adapt Prefabricated Switchgear to the High-Voltage Distribution Requirements of 10kv Photovoltaic Power Plants.
3. System Maintenance: Avoid costly downtime by reviewing our professional guide on Power Transformer Repair: How to Identify Repairable vs Non-Repairable Faults.
FAQ about SC(B) 13/14/18 Dry-Type Transformers
1. What is the main difference between SCB13, SCB14, and SCB18 dry transformers?
The primary difference lies in their energy efficiency levels and core loss reduction. Our SCB18 series meets Level 1 energy efficiency standards, reducing no-load losses by up to 20-25% compared to the SCB13, which translates to massive long-term operational savings for your project.
2. Can your resin-insulated dry transformers operate in 100% humidity?
Yes, absolutely. Because our copper/foil windings are completely encapsulated in vacuum-cast epoxy resin, the coils do not absorb moisture. You can safely deploy them in 100% relative humidity and harsh environments without any pre-drying or “tide treatment” after idle periods.
3. Why should I choose a cast resin transformer over an oil-immersed transformer?
Cast resin transformers offer superior fire and explosion safety (self-extinguishing glass fiber insulation), making them ideal for high-density indoor spaces like subways, hospitals, and commercial centers. Additionally, you eliminate oil leakage risks, rendering them virtually maintenance-free.
4. What cooling options are available for your power transformers?
We provide two operational modes: Natural Air Cooling (AN) for standard, continuous load operations, and Forced Air Cooling (AF). With our integrated AF cooling system, you can increase the short-term overload capacity of your transformer by up to 40-50% for peak safety.
5. Do you provide custom voltage combinations and tap ranges?
Yes, we design for your specific grid matrix. Our standard line supports high voltage ratings of 6.3kV, 10kV, 20kV, and 24kV with tap ranges of ±5% or ±2×2.5%, stepping down to a low voltage of 0.4kV with standard Dyn11 or Yyn0 connection groups.