Visión general
FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current. It is mainly used in urban distribution power stations and industrial electrical equipment for three-phase ring network or terminal power supply. For responsible control and short circuit protection purposes.
Modelo Significado
F |
N |
12 |
|
12 |
D |
/ |
630 |
– |
20 |
– |
□ |
↓ |
↓ |
↓ |
|
↓ |
↓ |
|
↓ |
|
↓ |
|
↓ |
Ac high
voltage load
interruptor |
Interior |
Diseño
secuencia
número |
|
Rated
voltage(KV) |
Ground
interruptor |
|
Rated active
load current
(A) |
|
Rated heat
stable
corriente(kA) |
|
Mechanical
form:S hand
exercise;
D motor |
F |
N |
|
|
12 |
(R) |
D |
1 |
125 |
|
31.5 |
|
□ |
↓ |
↓ |
↓ |
|
↓ |
↓ |
↓ |
|
↓ |
|
↓ |
|
↓ |
Ac high voltage load switch-fuse combination appliance |
Interior |
Número de secuencia del diseño |
|
Tensión nominal (KV) |
With a fuse |
Ground switch |
|
Rated active load current(A) |
|
Rated heat stable current (kA) |
|
Mechanical form: S hand exercise; D motor |
Principales parámetros técnicos
Artículo |
Unidades |
FN 12-120/630 |
FN12-12RD/125-31.5 |
Tensión nominal |
KV |
12 |
12 |
Frecuencia nominal |
Hz |
50 |
50 |
Corriente nominal |
A |
630 |
100 |
Tensión soportada al impulso del rayo |
KV |
Ground and interphase 75, isolation fracture 85 |
|
1 min power frequency withstand voltage |
kV |
Ground and interphase 42,isolation fr |
acture 48 |
Rated heat stable current |
kA |
20(4S) |
|
Rated dynamic stable current |
KA |
50 |
|
Rated closing current(peak) |
kA |
50 |
|
Corriente asignada de corte en cortocircuito |
kA |
|
31.5 |
Rated transfer current |
kA |
|
15 |
Disconnect no-load transformer capacity |
kVA |
1250 |
1250 |
Rated cable charging current |
A |
10 |
10 |
Rated active load current breaking times |
tiempo |
10000 |
10000 |
Impactor trigger load switch opening time |
s |
|
<0.06 |
Ground switch heat stabilized current |
KA |
20(28) |
|
Ground switch dynamic stable current |
KA |
50 |
|
Operating power supply |
|
110、220 |
110、220 |
Product Structure Diagram


Modelo |
A |
H |
C |
D |
E |
F |
K |
J |
L |
M |
N |
P |
R |
S |
T |
U |
V |
W |
Z |
Peso |
FN12-12RD |
376 |
945 |
600 |
210 |
648 |
270 |
67 |
50 |
170 |
287 |
165 |
357 |
11 |
335 |
170 |
99 |
105 |
590 |
180 |
70KG |