FN12-12D/T630-20, FN12-12DR/T125-31.5 Indoor AC High Voltage Load Break Switch With Fuse
FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current.
FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current. It is mainly used in urban distribution power stations and industrial electrical equipment for three-phase ring network or terminal power supply. For responsible control and short circuit protection purposes.
Model Meaning
F
N
12
12
D
/
630
–
20
–
□
↓
↓
↓
↓
↓
↓
↓
↓
Ac high
voltage load
switch
Indoor
Design
sequence
number
Rated
voltage(KV)
Ground
switch
Rated active
load current
(A)
Rated heat
stable
current(kA)
Mechanical
form:S hand
exercise;
D motor
F
N
12
(R)
D
1
125
31.5
□
↓
↓
↓
↓
↓
↓
↓
↓
↓
Ac high voltage load switch-fuse combination appliance
Indoor
Design sequence number
Rated voltage (KV)
With a fuse
Ground switch
Rated active load current(A)
Rated heat stable current (kA)
Mechanical form: S hand exercise; D motor
Main Technical Parameters
Item
Units
FN 12-120/630
FN12-12RD/125-31.5
Rated voltage
KV
12
12
Rated frequency
Hz
50
50
Rated current
A
630
100
Lightning impulse withstand voltage
KV
Ground and interphase 75, isolation fracture 85
1 min power frequency withstand voltage
kV
Ground and interphase 42,isolation fr
acture 48
Rated heat stable current
kA
20(4S)
Rated dynamic stable current
KA
50
Rated closing current(peak)
kA
50
Rated short-circuit breaking current
kA
31.5
Rated transfer current
kA
15
Disconnect no-load transformer capacity
kVA
1250
1250
Rated cable charging current
A
10
10
Rated active load current breaking times
time
10000
10000
Impactor trigger load switch opening time
s
<0.06
Ground switch heat stabilized current
KA
20(28)
Ground switch dynamic stable current
KA
50
Operating power supply
110、220
110、220
Product Structure Diagram
Model
A
H
C
D
E
F
K
J
L
M
N
P
R
S
T
U
V
W
Z
Weight
FN12-12RD
376
945
600
210
648
270
67
50
170
287
165
357
11
335
170
99
105
590
180
70KG
WE ARE HERE TO SUPPORT YOU!
Further information or a personal consultation? Our products and know-how