Overview
FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current. It is mainly used in urban distribution power stations and industrial electrical equipment for three-phase ring network or terminal power supply. For responsible control and short circuit protection purposes.
Model Meaning
| F |
N |
12 |
|
12 |
D |
/ |
630 |
– |
20 |
– |
□ |
| ↓ |
↓ |
↓ |
|
↓ |
↓ |
|
↓ |
|
↓ |
|
↓ |
Ac high
voltage load
switch |
Indoor |
Design
sequence
number |
|
Rated
voltage(KV) |
Ground
switch |
|
Rated active
load current
(A) |
|
Rated heat
stable
current(kA) |
|
Mechanical
form:S hand
exercise;
D motor |
| F |
N |
|
|
12 |
(R) |
D |
1 |
125 |
|
31.5 |
|
□ |
| ↓ |
↓ |
↓ |
|
↓ |
↓ |
↓ |
|
↓ |
|
↓ |
|
↓ |
| Ac high voltage load switch-fuse combination appliance |
Indoor |
Design sequence number |
|
Rated voltage (KV) |
With a fuse |
Ground switch |
|
Rated active load current(A) |
|
Rated heat stable current (kA) |
|
Mechanical form: S hand exercise; D motor |
Main Technical Parameters
| Item |
Units |
FN 12-120/630 |
FN12-12RD/125-31.5 |
| Rated voltage |
KV |
12 |
12 |
| Rated frequency |
Hz |
50 |
50 |
| Rated current |
A |
630 |
100 |
| Lightning impulse withstand voltage |
KV |
Ground and interphase 75, isolation fracture 85 |
|
| 1 min power frequency withstand voltage |
kV |
Ground and interphase 42,isolation fr |
acture 48 |
| Rated heat stable current |
kA |
20(4S) |
|
| Rated dynamic stable current |
KA |
50 |
|
| Rated closing current(peak) |
kA |
50 |
|
| Rated short-circuit breaking current |
kA |
|
31.5 |
| Rated transfer current |
kA |
|
15 |
| Disconnect no-load transformer capacity |
kVA |
1250 |
1250 |
| Rated cable charging current |
A |
10 |
10 |
| Rated active load current breaking times |
time |
10000 |
10000 |
| Impactor trigger load switch opening time |
s |
|
<0.06 |
| Ground switch heat stabilized current |
KA |
20(28) |
|
| Ground switch dynamic stable current |
KA |
50 |
|
| Operating power supply |
|
110、220 |
110、220 |
Product Structure Diagram


| Model |
A |
H |
C |
D |
E |
F |
K |
J |
L |
M |
N |
P |
R |
S |
T |
U |
V |
W |
Z |
Weight |
| FN12-12RD |
376 |
945 |
600 |
210 |
648 |
270 |
67 |
50 |
170 |
287 |
165 |
357 |
11 |
335 |
170 |
99 |
105 |
590 |
180 |
70KG |