FN12-12D/T630-20, FN12-12DR/T125-31.5 Indoor AC High Voltage Load Break Switch With Fuse

FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current.

Get A Quote Data Download
Product Overview

Overview

FN12-12 and FN12-12RD combined electrical appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz, which are used for switching load current, closed-loop current no-load transformer and cable charging current, closing short-circuit current, and load switch equipped with ground switch, which can withstand short-circuit current. It is mainly used in urban distribution power stations and industrial electrical equipment for three-phase ring network or terminal power supply. For responsible control and short circuit protection purposes.

 

Model Meaning

F N 12 12 D / 630 20
Ac high
voltage load
switch
Indoor Design
sequence
number
Rated
voltage(KV)
Ground
switch
Rated active
load current
(A)
Rated heat
stable
current(kA)
Mechanical
form:S hand
exercise;
D motor

 

F N 12 (R) D 1 125 31.5
Ac high voltage load switch-fuse combination appliance Indoor Design sequence number Rated voltage (KV) With a fuse Ground switch Rated active load current(A) Rated heat stable current (kA) Mechanical form: S hand exercise; D motor

 

Main Technical Parameters

Item Units FN 12-120/630 FN12-12RD/125-31.5
Rated voltage KV 12 12
Rated frequency Hz 50 50
Rated current A 630 100
Lightning impulse withstand voltage KV Ground and interphase 75, isolation fracture 85
1 min power frequency withstand voltage kV Ground and interphase 42,isolation fr acture 48
Rated heat stable current kA 20(4S)
Rated dynamic stable current KA 50
Rated closing current(peak) kA 50
Rated short-circuit breaking current kA 31.5
Rated transfer current kA 15
Disconnect no-load transformer capacity kVA 1250 1250
Rated cable charging current A 10 10
Rated active load current breaking times time 10000 10000
Impactor trigger load switch opening time s <0.06
Ground switch heat stabilized current KA 20(28)
Ground switch dynamic stable current KA 50
Operating power supply 110、220 110、220

 

Product Structure Diagram

 

Model A H C D E F K J L M N P R S T U V W Z Weight
FN12-12RD 376 945 600 210 648 270 67 50 170 287 165 357 11 335 170 99 105 590 180 70KG

 

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
Get High And Low Voltage Power Transmission And Distribution Solutions Today !
X
icon
icon
icon