Overview
KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as “switchgear”) It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. The newly introduced and developed high current and high-breaking switchgear can also be used separately as a high-voltage generator outlet.
This product conforms to the standards: GB3906 “3~35kV AC metal enclosed switchgear”, GB/T11022 “High voltage switchgear and control equipment standard common technical requirements”, IEC298 “rated voltage above 1kV 52kV and below AC metal enclosed switchgear and control equipment”.
Model Meaning
K | Y | N | 28 | – | 12 | Z |
↓ | ↓ | ↓ | ↓ | | ↓ | ↓ |
Metal armoured type | Shifting type | Indoor | Design sequence number | | Rated voltage (KV) | Vacuum circuit breaker |
Conditions Of Uuse
• Ambient air temperature: maximum temperature +40℃ , minimum temperature -15℃ ;
• Relative humidity: daily average relative humidity: ≤ 95%, daily average water vapor pressure does not exceed 2.2KPa; Monthly average relative humidity ≤ 90%; The average monthly steam pressure does not exceed 1.8KPa;
• Altitude: ≤ 1000m;
• Seismic intensity: not more than 8;
• The surrounding air should be free from corrosive or flammable gas, water vapor and other obvious pollution;
• No violent vibration site;
• When used under normal conditions beyond GB3906, the user and the company shall negotiate.
KYN28-12 Armored Withdrawable Type AC Metal-Enclosed Switchgear
Parameter | Unit | Value |
Rated Voltage | KV | 3.6、7.2、12 |
Rated Frequency | Hz | 50 |
Rated current of circuit breaker | A | 630、1250、1600、2000、2500、3150、4000 |
Rated current of switchgear | A | 630、1250、1600、2000、2500、3150、4000 |
Rated Short-time Withstand Current (4s) | KA | 16、20、25、31.5、40、50 |
Rated Peak Withstand Current (Peak Value) | KA | 40、50、63、80、100、125 |
Rated Short-Circuit Breaking Current | KA | 16、20、25、31.5、40、50 |
Rated Short-Circuit Making Current(Peak Value) | KA | 40、50、63、80、100、125 |
Rated
Insulation
Level | 1min Power Frequency
Withstand Voltage
Rated | Phase to phase,phase to earth
Gaps | KV | 24、32、42 |
KV | 24、32、48 |
Lightning Impulse
Withstand Voltage
(Peak) | Phase to phase,phase to earth
Gaps | KV | 40、60、75 |
KV | 46、70、85 |
Protection (IP)Rating | | IP4X |