Chuanli is a professional oil immersed transformer manufacturer supplying S13, S20, S22 series fully-sealed distribution transformers for 6kV-24kV power systems. S13/S20/S22 series fully sealed oil-immersed transformers are suitable for power systems with AC 50Hz and rated working voltage of 20kV and below, as the power distribution of petroleum, metallurgy, chemical, textile, light industry and other enterprises and places with heavy dust transformer. Get a transformer quotation today.
Signification du modèle
| S | □ | – | M | □ | / | □ |
| ↓ | ↓ | ↓ | ↓ | | | ↓ |
| Triphasé | Numéro d'ordre du dessin ou modèle | | Joint complet | Capacité (kVA) | | Côté haute pression Niveau de tension |
Transformer Standards & Certifications
Our oil immersed transformers comply with international and national standards:
GB1094.1-1996 GB 1094.2-1996 JB/T10088-2004
GB1094.3-2003 GB 1094.5-2003 GB/T10237-1988
GB/T6451-1999 GB/T 7595-1987 JB/T3837-1998
Technical Operating Conditions
Température ambiante : Maximum +40℃ , Minimum -25℃ (type extérieur) / -5℃ (type intérieur).
Altitude : L'altitude du site d'installation ne doit pas dépasser 1000 mètres.
Humidité relative : Moyenne journalière ≤ 95%, Moyenne mensuelle ≤ 90%.
Intensité sismique : Ne dépassant pas 8 degrés.
Environnement d'installation : Pas d'incendie, de risques d'explosion, de pollution grave, de corrosion chimique ou de vibrations intenses.
Méthode de refroidissement : ONAN (Oil Natural Air Natural) ou ONAF (Oil Natural Air Forced).
Fréquence : Fréquence nominale 50Hz ou 60Hz.
Tension nominale : Elle doit correspondre au niveau de tension du système, généralement 6kV, 10kV, 20kV, 35kV, etc.
Key Features of Our Oil Immersed Transformers
● Noyau : Le noyau est fabriqué en acier au silicium laminé à froid à grain orienté à haute perméabilité. Le noyau du nouveau noyau, joints d'onglet convolution type de fer, ses jambes de section circulaire multiétapes, l'empiècement et le noyau de section constante.
● Enroulement : Les enroulements ondulés passage de l'huile, pas le processus de trempage, le serrage de l'arrimage de la courroie ; bobines concentriques sont : enroulement haute tension a un robinet correspondant exigences de tension, conduire à un robinet sur le commutateur, le commutateur est monté sur le couvercle, et la nécessité de couper Après l'alimentation électrique avant de convertir le robinet de tension.
● Dispositifs de sécurité:Transformateur 30~2000kVA équipé d'une soupape de décompression ; Peut être installé avec des bornes de gaz d'alarme et de relais de déclenchement selon les besoins de l'utilisateur ;
● Dispositif de mesure de la température de l'huile:Les transformateurs Headers sont équipés d'un thermomètre en verre, douille de tube située sur le dessus du réservoir, insérée dans l'huile 120±10mm ; type de transformateur 1000~2000kVA équipé d'un signal de thermomètre extérieur ;
● Réservoir de transformateur : La cuve du transformateur est constituée de parois ondulées. La surface est pulvérisée de poussière et le film de peinture est ferme. Les ailettes ondulées ont non seulement une fonction de refroidissement, mais aussi une fonction de "respiration". L'élasticité des ailettes ondulées peut compenser le changement de volume de l'huile du transformateur causé par l'augmentation et la diminution de la température. Par conséquent, le transformateur entièrement étanche n'a pas d'armoire de stockage d'huile, ce qui réduit la hauteur totale du transformateur ;
● Le transformateur est rempli sous vide pendant l'emballage, ce qui élimine complètement l'humidité dans le transformateur, et l'huile du transformateur n'est pas en contact avec l'air. Empêcher efficacement l'oxygène et l'humidité de pénétrer dans le transformateur, ce qui entraîne une diminution des performances d'isolation du transformateur et la possibilité de vieillissement de l'huile de transformateur, de sorte que le test de l'échantillon d'huile est effectué de manière irrégulière ;
Transformateur de distribution à bain d'huile de type S13-M 6~10kV
Capacité nominale (KVA) | Combinaison de tensions et plage de prises | Vecteur symbole du groupe | Sans charge perte(W) | Perte de charge (W) | Sans charge actuel (%) | Court-circuit impédance (%) |
Haute pression (kV) | Haute pression plage de prise (%) | Basse pression ( KV) |
| 30 | 6 6.3 6.6 10 10.5 11 | ±5%
±2×2.5% | 0.4 | Dyn11
Yzn11Yyn0 | 80 | 630/600 | 1.8 | 4 |
| 50 | 100 | 910/870 | 1.6 | 4 |
| 63 | 110 | 1090/1040 | 1.6 | 4 |
| 80 | 130 | 1310/1250 | 1.5 | 4 |
| 100 | 150 | 1580/1500 | 1.4 | 4 |
| 125 | 170 | 1890/1800 | 1.4 | 4 |
| 160 | 200 | 2310/2200 | 1.3 | 4 |
| 200 | 240 | 2730/2600 | 1.2 | 4 |
| 250 | 290 | 3200/3050 | 1.2 | 4 |
| 315 | 340 | 3830/3650 | 1.1 | 4 |
| 400 | 410 | 4520/4300 | 1.1 | 4 |
| 500 | 480 | 5410/5150 | 1 | 4 |
| 630 | 570 | 6200 | 0.9 | 4.5 |
| 800 | Dzn11 Yyn0 | 700 | 7500 | 0.8 | 4.5 |
| 1000 | 830 | 10300 | 0.8 | 4.5 |
| 1250 | 970 | 12000 | 0.7 | 4.5 |
| 1600 | 1170 | 14500 | 0.6 | 4.5 |
Capacité nominale (KVA) | Combinaison de tensions et plage de prises | Vecteur symbole du groupe | Sans charge perte(W) | Perte de charge (W) | Sans charge actuel (%) | Court-circuit impédance (%) |
Haute pression (kV) | Haute pression plage de prise (%) | Basse pression (KV) |
| 50 | 20
22
24 | ±5
±2×2.5% | 0.4 | Dyn11
Yyn0 | 170 | 1270/1210 | 2.00 | 6.5 |
| 100 | 230 | 2120/2020 | 1.80 | 6.5 |
| 125 | 270 | 2500/2380 | 1.70 | 6.5 |
| 160 | 290 | 2970/2830 | 1.60 | 6.5 |
| 200 | 340 | 3500/3330 | 1.50 | 6.5 |
| 250 | 410 | 4160/3960 | 1.40 | 6.5 |
| 315 | 490 | 5010/4770 | 1.40 | 6.5 |
| 400 | 580 | 6050/5760 | 1.30 | 6.5 |
| 500 | 690 | 7280/6930 | 1.20 | 6.5 |
| 630 | 830 | 8280 | 1.10 | 6.5 |
| 800 | 980 | 9900 | 1.00 | 6.5 |
| 1000 | 1150 | 12150 | 1.00 | 6.5 |
| 1250 | 1410 | 14670 | 0.90 | 6.5 |
| 1600 | 1700 | 17550 | 0.80 | 6.5 |
Remarque :
1. La perte de charge au-dessus de la ligne oblique dans le tableau s'applique au groupe de connexion Dyn11, et la valeur de la perte de charge au-dessous de la ligne oblique s'applique au groupe de connexion Yyn0.
2. Autre capacité des paramètres de performance du produit, déterminée par l'utilisateur et le fabricant.
L'huile S20M devient économe en énergie de niveau 2
| Capacité nominale (kVA) | Perte à vide (W) | Perte de charge (W) | Courant à vide (%) | Dimensions (mm) |
| 30 | 70 | 505 | 0.015 | 770*415*860 |
| 50 | 90 | 730 | 0.013 | 820*565*910 |
| 80 | 115 | 1050 | 0.012 | 860*600*950 |
| 100 | 135 | 1265 | 0.011 | 880*630*970 |
| 125 | 150 | 1510 | 0.011 | 890*670*1030 |
| 160 | 180 | 1850 | 0.01 | 920*690*1050 |
| 200 | 215 | 2185 | 0.01 | 940*685*1070 |
| 250 | 260 | 2560 | 0.009 | 965*710*1100 |
| 315 | 305 | 3065 | 0.009 | 1165*725*1140 |
| 400 | 370 | 3615 | 0.008 | 1195*745*1170 |
| 500 | 430 | 4330 | 0.008 | 1195*750*1220 |
| 630 | 510 | 4960 | 0.006 | 1285*830*1250 |
| 800 | 630 | 6000 | 0.006 | 1390*915*1280 |
| 1000 | 745 | 8240 | 0.006 | 1600*1130*1290 |
| 1250 | 870 | 9600 | 0.005 | 1625*1125*1350 |
| 1600 | 1050 | 11600 | 0.005 | 1700*1175*1430 |
| 2000 | 1225 | 14640 | 0.004 | 1860*1325*1470 |
| 2500 | 1440 | 14840 | 0.004 | 1860*1235*1630 |
S22M Oil To Level 1 Efficacité énergétique
| Capacité nominale (kVA) | Perte à vide (W) | Perte de charge (W) | Courant à vide (%) | Dimensions (mm) |
| 30 | 65 | 455 | 0.015 | 815*430*860 |
| 50 | 80 | 655 | 0.013 | 860*460*930 |
| 80 | 105 | 945 | 0.012 | 910*625*970 |
| 100 | 120 | 1140 | 0.011 | 940*645*1010 |
| 125 | 135 | 1360 | 0.011 | 950*660*1080 |
| 160 | 160 | 1665 | 0.01 | 965*680*1110 |
| 200 | 190 | 1970 | 0.01 | 995*695*1130 |
| 250 | 230 | 2300 | 0.009 | 1015*715*1150 |
| 315 | 270 | 2760 | 0.009 | 1185*725*1180 |
| 400 | 330 | 3250 | 0.008 | 1250*785*1210 |
| 500 | 385 | 3900 | 0.008 | 1270*810*1280 |
| 630 | 460 | 4460 | 0.006 | 1325*855*1310 |
| 800 | 560 | 5400 | 0.006 | 1355*870*1330 |
| 1000 | 665 | 7415 | 0.006 | 1460*970*1350 |
| 1250 | 780 | 8640 | 0.005 | 1535*1005*1390 |
| 1600 | 940 | 10440 | 0.005 | 1610*1060*1500 |
| 2000 | 1085 | 13180 | 0.004 | 1740*1165*1550 |
| 2500 | 1280 | 13360 | 0.004 | 1830*1155*1730 |
FAQs About Oil Immersed Transformers
What oil immersed transformer series does Clelek offer?
Chuanli manufactures three series: S13 (standard efficiency), S20 (Level 2 energy efficient), and S22 (Level 1 premium energy efficient). All are fully-sealed corrugated tank design for 6kV to 24kV power systems.
What is the capacity range for your transformers?
Our standard capacity range is 30kVA to 2500kVA. 6kV-10kV and 20kV-24kV voltage ratings available. Custom capacities available upon request for special projects.
What is the difference between S13, S20, and S22 efficiency?
Compared to S13 baseline: S20 delivers 20% lower no-load loss (Level 2 efficiency), S22 delivers 30% lower no-load loss (Level 1 premium efficiency). S22 provides lowest TCO over 30-year lifespan.
What vector groups and tap ranges are available?
Standard vector groups: Dyn11, Yyn0, Yzn11, Dzn11. Tap ranges: ±5% or ±2×2.5% as standard. Custom configurations available.
What standards do your transformers comply with?
Manufactured to GB1094, GB/T6451, JB/T3837 standards, fully compatible with IEC 60076 international standards. CE certification available for export projects.
What cooling methods are available?
Standard cooling: ONAN (Oil Natural Air Natural). Optional ONAF (Oil Natural Air Forced) with fans for higher capacity applications. Custom cooling solutions on request.
What are the environmental operating limits?
Operating temperature: -25°C to +40°C outdoor, -5°C to +40°C indoor. Maximum altitude: 1000m. Seismic intensity: up to 8 degrees.
What safety features are included?
Standard features: pressure release valve (30-2000kVA), oil temperature gauge. Optional: gas relay with alarm and trip functions. Fully sealed design eliminates oil maintenance.
What is typical delivery lead time?
Standard models (30kVA-1600kVA): 10-15 working days. Larger capacities or custom designs: 20-30 working days. Container load orders receive priority scheduling.
Do you provide OEM and custom design services?