KYN28-12 Armored Withdrawable Type AC Metal-Enclosed Switchgear

KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as “switchgear”) It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. The newly introduced and developed high current and high-breaking switchgear can also be used separately as a high-voltage generator outlet.

Get A Quote Data Download
Product Overview

Product Overview: What Is the KYN28-12 Metal-Enclosed Switchgear?

KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as “switchgear”) It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. The newly introduced and developed high current and high-breaking switchgear can also be used separately as a high-voltage generator outlet.

This product conforms to the standards: GB3906 “3~35kV AC metal enclosed switchgear”, GB/T11022 “High voltage switchgear and control equipment standard common technical requirements”, IEC298 “rated voltage above 1kV 52kV and below AC metal enclosed switchgear and control equipment”.

 

KYN28-12 Model Number Explained

K Y N 28 12 Z
Metal armoured type Shifting type Indoor Design sequence number Rated voltage (KV) Vacuum circuit breaker

 

Installation & Operating Conditions

• Ambient air temperature: maximum temperature +40℃ , minimum temperature -15℃ ;

• Relative humidity: daily average relative humidity: ≤ 95%, daily average water vapor pressure does not exceed 2.2KPa; Monthly average relative humidity ≤ 90%; The average monthly steam pressure does not exceed 1.8KPa;

• Altitude: ≤ 1000m;

• Seismic intensity: not more than 8;

• The surrounding air should be free from corrosive or flammable gas, water vapor and other obvious pollution;

• No violent vibration site;

• When used under normal conditions beyond GB3906, the user and the company shall negotiate.

 

KYN28-12 Technical Specifications & Rated Parameters

Parameter Unit Value
Rated Voltage KV 3.6、7.2、12
Rated Frequency Hz 50
Rated current of circuit breaker A 630、1250、1600、2000、2500、3150、4000
Rated current of switchgear A 630、1250、1600、2000、2500、3150、4000
Rated Short-time Withstand Current (4s) KA 16、20、25、31.5、40、50
Rated Peak Withstand Current (Peak Value) KA 40、50、63、80、100、125
Rated Short-Circuit Breaking Current KA 16、20、25、31.5、40、50
Rated Short-Circuit Making Current(Peak Value) KA 40、50、63、80、100、125
Rated
Insulation
Level
1min Power Frequency
Withstand Voltage
Rated
Phase to phase,phase to earth
Gaps
KV 24、32、42
KV 24、32、48
Lightning Impulse
Withstand Voltage
(Peak)
Phase to phase,phase to earth
Gaps
KV 40、60、75
KV 46、70、85
Protection (IP)Rating IP4X

FAQs

What is the rated voltage and current range of the KYN28-12 switchgear?
The KYN28-12 armored withdrawable metal-enclosed switchgear supports rated voltages of 3.6kV, 7.2kV, and 12kV, with rated current options ranging from 630A to 4000A. The rated short-circuit breaking current goes up to 50kA, making it suitable for high-demand industrial substations and utility power distribution networks. You can download the full technical datasheet to compare parameter configurations for your project.

Which international standards does the KYN28-12 comply with?
The KYN28-12 is fully compliant with three major standards: GB3906 (3~35kV AC metal-enclosed switchgear), GB/T11022 (common technical requirements for high-voltage switchgear and control equipment), and IEC298 (AC metal-enclosed switchgear for rated voltages above 1kV up to and including 52kV). If your project requires documentation for customs clearance or engineering approval, you can request certified test reports from our team.

What are the installation environment requirements for the KYN28-12?
The KYN28-12 is designed for indoor installation at altitudes up to 1000m. The ambient temperature must be between −15°C and +40°C, with relative humidity not exceeding 95% (daily average) or 90% (monthly average). The installation site must be free from corrosive or flammable gases, water vapor, and significant vibration. For projects in high-altitude or extreme-climate regions, please contact us to discuss customized configurations.

Can the KYN28-12 be used as a high-voltage generator outlet?
Yes. The newly developed high-current, high-breaking version of the KYN28-12 can be deployed independently as a high-voltage generator outlet switchgear panel, in addition to standard incoming and outgoing feeder configurations. This makes it a versatile choice for power station projects and cogeneration facilities. Our engineering team can advise on the appropriate circuit breaker and busbar configuration for your generator output requirements.

How do I request a quote or technical consultation for the KYN28-12?
You can submit your inquiry directly through the “Get A Quote” form on this page. To accelerate the quotation process, it helps to provide your required rated voltage, current, number of panels, installation location, and applicable standards. Our technical sales team typically responds within 24 hours. You can also download the KYN28-12 datasheet to review full specifications before reaching out.

WE ARE HERE TO SUPPORT YOU!

Further information or a personal consultation? Our products and know-how are there to provide solutions.

RELATED PRODUCTS
RELATED NEWS
YOU MAY ALSO WANT TO SEE
Get High And Low Voltage Power Transmission And Distribution Solutions Today !
X
icon
icon
icon
en_US