Wider TUR distribution board for 630 kVA transformers. Dimensions 1450 x 900 x 450 mm, fixing centres 760 ± 20 mm horizontal and 590 mm vertical. Same cable options as TR5-1200I: 2 x 240 mm² or 1 x 630 mm² per phase. More internal space for installation and monobloc feeders.

Obter uma cotação Download de dados
Visão geral do produto

The TR8-1200I is a TUR distribution board for 630 kVA transformer connections, featuring a wider format of 1450 x 900 x 450 mm and recommended fixing centres of 760 ± 20 mm horizontally and 590 mm vertically. It supports the same cable configurations as the TR5-1200I: 2 x 240 mm² or 1 x 630 mm² per phase, and 1 x 240 mm² or 1 x 630 mm² for the neutral. The wider design provides more internal space for installation and for mounting monobloc outgoing feeders. It also includes the main switch handle, lockable open position, and options such as protection screens and reservation panels. It is suitable for installations that require a larger layout while maintaining 630 kVA capacity.

 

Principais parâmetros técnicos

Main mechanical parameters

Item Unidade Parâmetro
Corrente nominal A 1200
Dimensions (H x W x D) mm 1450 x 900 x 450
Recommended Fixing Centers (H / V) mm 760±20 / 590
Fixing Holes – 4 x M14
Transformer Power kVA 630
Recommended Cable per Phase (ALU) mm² 2 x 240 or 1 x 630
Recommended Neutral Cable (ALU) mm² 1 x 240 or 1 x 630
Fuse Type – T2 (115mm, 440V)
Barramentos Nm N, Ph1, Ph2, Ph3
Mounting Type – Wall-mounted
Switch Handle Position mm² Up=Closed(Red) / Down=Open(Green)
MALT Earthing Torque Nm 30±5
Handle Mounting Torque Nm 20±5
Upstream Connection Torque Nm –
Side Panels Torque Nm 30±5
Monobloc Outgoing Feeder Torque Nm 30±5

Functional Features:

  • Electrical function: suitable for a 630 kVA transformer LV main incoming/main switch; switch rated current 1200 A.

  • Connection capability: recommended phase cable 2 × 240 mm² or 1 × 630 mm² Alu; neutral cable 1 × 240 mm² or 1 × 630 mm² Alu.

  • Operation: manual switch operation; handle up = CLOSED (red), down = OPEN (green); padlocking possible in the OPEN position.

  • Safety and protection: earthing connection; side panels, horizontal protection screen, removable screen to prevent direct contact with live parts.

  • Expansion: optional EP lighting, ACG general switch, reservation panel, monobloc outgoing units, fuse protection.

  • Difference: horizontal protection screen mounted via a screen support bracket.