DBT Microbloc Simple Ratio Three-Phase Monobloc Current Transformer for Low Voltage Metering (25 to 600A)

The DBT Microbloc is a compact, three-phase monobloc current transformer designed for low voltage metering applications. It supports primary currents from 25A to 600A, allows parallel cable passage, and integrates current transformers, voltage terminals, fuses, and short-circuiters in a single sealed unit.

Aperçu du produit

Vue d'ensemble

The Microbloc is built with a shock-resistant, unbreakable, and self-extinguishing molded housing and covers, with all metal parts treated for corrosion resistance. It is designed to allow multiple cables to pass through in parallel. The device complies with NFC42-502, NF EN 60044-1, and EDF specification HN 42 S 55 (1971).

The Microbloc assembly includes:

  • 3 current transformers.

  • 4 phase and neutral voltage terminals.

  • 3 HPC 10A fuse circuit breakers on the phase voltage terminals.

  • 3 short-circuiters for the current transformer secondary circuits.

  • 1 secondary terminal block with clear connection markings.

  • 1 sealable transparent cover equipped with a rotatable nameplate and 3 safety interlocks that prevent the cover from being replaced if the 3 fuses are not reinstalled on the voltage circuits.

Features and Functions

  • Allows several cables to pass in parallel.

  • Complies with NFC42-502, NF EN 60044-1 and EDF specification HN 42 S 55 (1971).

  • Three-phase monobloc design for low voltage metering.

  • Primary currents available: 25, 30, 50, 75, 100, 125, 150, 200, 250, 300, 400, 500, 600 A.

  • Accuracy power: 3 × 3.75 VA to 3 × 15 VA.

  • Accuracy class: 0.5; optional 0.2S at 3 × 3.75 VA and 3 × 7.5 VA.

  • The Microbloc includes:

    • 3 current transformers.

    • 4 phase and neutral voltage terminals.

    • 3 HPC 10 A fuse circuit breakers on phase voltage terminals.

    • 3 short-circuiters for CT secondary circuits.

    • 1 secondary terminal block with clear connection markings.

    • 1 sealable transparent cover with a rotatable nameplate and 3 interlocks preventing cover replacement if the 3 fuses are not reinstalled on voltage circuits.

 

Technical Specifications

Product Type Three-Phase Monobloc Current Transformer
Application Low Voltage Metering
Standards NFC42-502, NF EN 60044-1, EDF HN 42 S 55 (1971)
Fréquence nominale 50 Hz
Rated Insulation Voltage 0.6 kV
Highest Voltage for Equipment 0.72 kV
Power Frequency Withstand Voltage (1 min) 3 kV
Impulse Withstand Voltage 8 kV (1.2/50 μs)
Secondary Winding Insulation Class H
Housing Insulation Class E
Primary Currents (Ipn) 25, 30, 50, 75, 100, 125, 150, 200, 250, 300, 400, 500, 600 A
Continuous Thermal Current 1.2 Ipn
Thermal Short-Circuit Current (Ith) 80 Ipn / 1s
Secondary Currents 5 A
Accuracy Power 3×3.75 VA to 3×15 VA
Accuracy Class 0.5 (Optional 0.2S at 3×3.75 VA and 3×7.5 VA)
Poids 7 kg
Dimensions (L x W x H) Approx. 339 x 209 x 107 mm
Mounting Holes 4 x Ø9 mm

Dimensional and Mounting Drawing

 

 

NOUS SOMMES LÀ POUR VOUS SOUTENIR !