KYN28-12 Aparamenta metálica blindada de CA de tipo retráctil

KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as "switchgear") It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. La nueva aparamenta de alta corriente y alta ruptura introducida y desarrollada también puede utilizarse por separado como toma de generador de alta tensión.

Solicitar presupuesto Descarga de datos
Product Overview - Why KYN28-12 Is Your Best Choice for 12kV MV Distribution

KYN28-12 Key Applications & Operating Conditions

KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as "switchgear") It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. La nueva aparamenta de alta corriente y alta ruptura introducida y desarrollada también puede utilizarse por separado como toma de generador de alta tensión.

Este producto cumple las normas: GB3906 "3~35kV AC metal enclosed switchgear", GB/T11022 "High voltage switchgear and control equipment standard common technical requirements", IEC298 "rated voltage above 1kV 52kV and below AC metal enclosed switchgear and control equipment".

 

KYN28-12 Model Number Explained

K Y N 28 12 Z
Tipo blindado metálico Tipo de cambio Interior Número de secuencia del diseño Tensión nominal (KV) Interruptor de vacío

 

Installation & Operating Conditions

- Temperatura ambiente del aire: temperatura máxima +40℃ , temperatura mínima -15℃ ;

- Humedad relativa: humedad relativa media diaria: ≤ 95%, la presión media diaria del vapor de agua no supera los 2,2KPa; Humedad relativa media mensual ≤ 90%; La presión media mensual del vapor no supera los 1,8KPa;

- Altitud: ≤ 1000m;

- Intensidad sísmica: no superior a 8;

- El aire circundante debe estar libre de gases corrosivos o inflamables, vapor de agua y otras contaminaciones evidentes;

- No hay lugar para vibraciones violentas;

- Cuando se utilice en condiciones normales más allá de GB3906, el usuario y la empresa deberán negociar.

 

KYN28-12 Technical Specifications & Rated Parameters

Parámetro Unidad Valor
Tensión nominal KV 3.6、7.2、12
Frecuencia nominal Hz 50
Corriente nominal del disyuntor A 630、1250、1600、2000、2500、3150、4000
Corriente nominal de la aparamenta A 630、1250、1600、2000、2500、3150、4000
Corriente nominal de corta duración (4 s) KA 16、20、25、31.5、40、50
Corriente nominal de pico soportada (valor de pico) KA 40、50、63、80、100、125
Corriente nominal de corte en cortocircuito KA 16、20、25、31.5、40、50
Corriente nominal de cortocircuito (valor pico) KA 40、50、63、80、100、125
Rated
Aislamiento
Nivel
1min Potencia Frecuencia
Tensión soportada
Rated
Fase a fase, fase a tierra
Lagunas
KV 24、32、42
KV 24、32、48
Impulso del rayo
Tensión soportada
(Pico)
Fase a fase, fase a tierra
Lagunas
KV 40、60、75
KV 46、70、85
Grado de protección (IP) IP4X

Preguntas frecuentes

1: What is the rated voltage and frequency of the KYN28-12?
The KYN28-12 operates at 12kV rated voltage with 50/60Hz frequency—covering your standard medium voltage distribution requirements. It also supports 7.2kV and 40.5kV configurations in the KYN series family for broader network compatibility.
2: What does “armored withdrawable” mean vs. open-type switchgear?
“Armored” means each compartment is metal-separated—protecting your operators from arc faults during maintenance. “Withdrawable” allows you to pull out the circuit breaker truck for inspection or replacement without de-energizing the entire panel. This combination maximizes both your safety and operational continuity.
3: Does the KYN28-12 comply with IEC 62271?
Yes. The KYN28-12 is type-tested per IEC 62271-200 (AC metal-enclosed switchgear and controlgear for rated voltages above 1kV). Internal arc test classification is available for your personnel safety compliance. Full type-test reports are downloadable for your project review. → View certifications
4: What is the vacuum circuit breaker interruption time?
The integrated vacuum circuit breaker (VCB) achieves interruption in under 50ms—significantly faster than oil-type breakers. This rapid clearing protects your downstream equipment from sustained fault currents and reduces thermal stress on your busbar system.
5: Can you customize the KYN28-12 for my specific protection scheme?
Absolutely. As the direct manufacturer, we can configure your KYN28-12 with specific protection relay settings, CT/PT ratios, and interlocking logic. Custom busbar sizing, cable entry arrangements, and smart monitoring integration are also available.
6: What is the lead time for KYN28-12 delivery?
Standard KYN28-12 models ship within 15–20 working days. Custom protection configurations require 25–30 working days. We maintain in-stock VCB components and 8MF frame assemblies to shorten your delivery timeline for urgent projects. → Contact us for delivery schedule
ESTAMOS AQUÍ PARA APOYARLE

¿Desea más información o una consulta personal? Nuestros productos y conocimientos están ahí para ofrecerle soluciones.

PRODUCTOS RELACIONADOS
NOTICIAS RELACIONADAS
TAMBIÉN PUEDE VER
Obtenga hoy mismo soluciones de transmisión y distribución de energía de alta y baja tensión !