Visión general
KYN28-12(GZS1) type armoured removable AC metal enclosed switchgear (hereinafter referred to as "switchgear") It is suitable for three-phase AC 50Hz power system, used to receive and distribute electrical energy and control, protect and monitor the circuit. La nueva aparamenta de alta corriente y alta ruptura introducida y desarrollada también puede utilizarse por separado como toma de generador de alta tensión.
This product conforms to the standards: GB3906 “3~35kV AC metal enclosed switchgear”, GB/T11022 “High voltage switchgear and control equipment standard common technical requirements”, IEC298 “rated voltage above 1kV 52kV and below AC metal enclosed switchgear and control equipment”.
Modelo Significado
K |
Y |
N |
28 |
– |
12 |
Z |
↓ |
↓ |
↓ |
↓ |
|
↓ |
↓ |
Tipo blindado metálico |
Tipo de cambio |
Interior |
Número de secuencia del diseño |
|
Tensión nominal (KV) |
Interruptor de vacío |
Conditions Of Uuse
• Ambient air temperature: maximum temperature +40℃ , minimum temperature -15℃ ;
• Relative humidity: daily average relative humidity: ≤ 95%, daily average water vapor pressure does not exceed 2.2KPa; Monthly average relative humidity ≤ 90%; The average monthly steam pressure does not exceed 1.8KPa;
• Altitude: ≤ 1000m;
• Seismic intensity: not more than 8;
• The surrounding air should be free from corrosive or flammable gas, water vapor and other obvious pollution;
• No violent vibration site;
• When used under normal conditions beyond GB3906, the user and the company shall negotiate.
KYN28-12 Aparamenta metálica blindada de CA de tipo retráctil
Parameter |
Unidad |
Value |
Rated Voltage |
KV |
3.6、7.2、12 |
Frecuencia nominal |
Hz |
50 |
Rated current of circuit breaker |
A |
630、1250、1600、2000、2500、3150、4000 |
Rated current of switchgear |
A |
630、1250、1600、2000、2500、3150、4000 |
Rated Short-time Withstand Current (4s) |
KA |
16、20、25、31.5、40、50 |
Rated Peak Withstand Current (Peak Value) |
KA |
40、50、63、80、100、125 |
Rated Short-Circuit Breaking Current |
KA |
16、20、25、31.5、40、50 |
Rated Short-Circuit Making Current(Peak Value) |
KA |
40、50、63、80、100、125 |
Rated
Insulation
Level |
1min Power Frequency
Withstand Voltage
Rated |
Phase to phase,phase to earth
Gaps |
KV |
24、32、42 |
KV |
24、32、48 |
Lightning Impulse
Withstand Voltage
(Peak) |
Phase to phase,phase to earth
Gaps |
KV |
40、60、75 |
KV |
46、70、85 |
Protection (IP)Rating |
|
IP4X |