ZN63A(VS1)-24 Interruptor automático de vacío de alta tensión para interiores

La serie ZN63(VS1)-24 de interruptores automáticos de vacío de MT de CA para interiores es una aparamenta interior para sistemas de alimentación trifásica de CA 50Hz, tensión nominal 4KV.

Solicitar presupuesto Descarga de datos
Productos

Visión general

ZN63(VS1)-24 series indoor AC MV vacuum circuit breaker is an indoor switchgear for three-phase AC 50Hz, rated voltage 4KV power system. The market combines years of professional production experience to develop and design a new generation of vacuum circuit breakers.

 

Modelo Significado

VS 1 24 /
Indoor high voltage vacuum circuit breaker Product design serial number Tensión nominal (KV) Corriente nominal (A) Rated short circuit breaking current(kA)

 

Principales parámetros técnicos

Artículo Unidades Argumento
Tensión nominal kV 24
Rated short-term power frequency withstand voltage(1min) 65/79(alternating,facing ground/fracture)
Rated lightning impulse withstand voltage(peak value) 125/145(alternating,ground/fracture)
Frecuencia nominal Hz 50
Corriente nominal A 6301250 63012501600
200025003150
  63012501600
200025003150
Corriente asignada de corte en cortocircuito 20/25                   31.5                    40
Corriente nominal de corta duración kA 20/25                   31.5                    40
Rated short-circuit duration S 4
Corriente nominal de pico soportada 50/63                   80                       100
Corriente nominal de cierre en cortocircuito kA 50/63                   80                       100
Power frequency withstand voltage of the secondary circuit(1 minute) V 2000
Rated breaking current of single/back-to-back capacitor banks A 630/400(40kA is 800/400)
Rated capacitor bank closing inrush current kA 12.5(Frequency not exceeding 100OHz)
Vida mecánica Frequency 20000
Rated current breaking times(electrical life) 20000
Rated short-circuit current breaking times 50(40kA≤30)
The cumulative allowable wear thickness of the moving and static contacts mm 2
Energy storage time S ≤10
Distancia de apertura de los contactos mm 16±1
Overtravel 3.5±0.5
Contact closing and bouncing time ms ≤2
The asynchronous opening and closing of the three phases ≤2
Average opening speed(contact separation -8mm) m/s 1.5±0.2
Average closing speed (8mm-contact closure) 0.8±0.2
Resistance of the dominant electrical circuit μΩ ≤50(630A)≤45(1250A);≤35(1600-2000A)≤25(2500A)
Rated operating sequence Score-0.3 Combined score 180s-combined score

External Mounting Dimension (mm)

 

Tensión nominal Corriente nominal de ruptura Phase spacing A B C D
630A
1250A
1600A
25kA
31.5kA
40kA
210 652 682 638 277
275 852 882 838 377

 

Tensión nominal W
630A φ35
1250A φ49
1600A φ55

 