Core Components & Working Principle
The FZW32 load break switch features a disconnect blade, vacuum interrupter, and operation mechanism. Its vacuum arc-extinguishing chamber ensures rapid arc quenching, offering high reliability, long lifespan, and compact design. It is explosion-proof, pollution-free, and requires minimal maintenance.
Key Applications
Ideal for 12kV–45.5kV power distribution, the FZW32 is widely used in:
● Power Sector: Ensures stable grid transmission.
● Metallurgy: Supports high-power industrial machinery.
● Mining: Performs reliably in harsh, explosive environments.
● Chemical Plants: Resists corrosive conditions.
It excels in frequent-operation settings like substations and distribution centers.
Environmental Adaptability
Operates in diverse conditions:
● Altitude: Up to 2000m.
● Temperature: -30℃ to +40℃ (max daily variation: 32K).
● Wind Resistance: 700Pa (34m/s).
● Pollution: Grade IV (GB5585 standard).
● Durability: Withstands seismic intensity 8 and 10mm ice buildup.
Technical Specification:
| No. |
Item |
Unit |
Data |
| 1 |
Rated Voltage |
KV |
12 |
24 |
40.5 |
| 2 |
Rated Frequency |
Hz |
50 |
50 |
50 |
| 3 |
Rated Current |
A |
630 |
1250 |
1250 |
| 4 |
Rated Active Load Breaking Current |
A |
630 |
1250 |
1250 |
| 5 |
Rated Loop Breaking Current |
A |
630 |
1250 |
1250 |
| 6 |
5% Rated Active Load Breaking Current |
A |
31.5 |
62.5 |
62.5 |
| 7 |
Rated Cable Charging Breaking Current |
A |
10 |
10 |
25 |
| 8 |
Rated No-load Transformer Breaking Capacity |
KVA |
1600 |
1600 |
1600 |
| 9 |
Rated Breaking Current of Capacitor Bank |
A |
100 |
100 |
100 |
| 10 |
1-minute Power Frequency Withstand Voltage: Vacuum Break Phase-to-phase,Phase-to-ground/lsolation Break |
KV |
42/48 |
52/65 |
68/95/110 |
| 11 |
LightningImpulse Withstand Voltage: Phase-to-phasePhase-to-ground/lsolation Break |
KV |
78/85 |
125/145 |
185/215 |
| 12 |
Rated Short-time Withstand Current (Thermal Stability) |
KA |
20 |
20 |
25 |
| 13 |
Rated Short-circuit Duration |
s |
4 |
4 |
4 |
| 14 |
Rated Peak Withstand Current (Dynamic Stability) |
KA |
50 |
50 |
63 |
| 15 |
Rated Short-circuit Open-close Current |
KA |
50 |
50 |
63 |
| 16 |
Mechanical Life |
Times |
10000 |
10000 |
10000 |