TR5-1200I TUR Low Voltage Distribution Board

TUR distribution board for 630 kVA transformers. Dimensions 1450 x 650 x 450 mm, fixing centres 520 ± 20 mm horizontal and 590 mm vertical. Cable options: 2 x 240 mm² or 1 x 630 mm² per phase, and 1 x 240 mm² or 1 x 630 mm² for neutral. Flexible connection, lockable switch and monobloc feeders.

Solicitar presupuesto Descarga de datos
Productos

The TR5-1200I is a TUR distribution board for 630 kVA transformer connections. Its dimensions are 1450 x 650 x 450 mm, with recommended fixing centres of 520 ± 20 mm horizontally and 590 mm vertically. It offers flexible cable connection options: 2 x 240 mm² or 1 x 630 mm² aluminium cable per phase, and 1 x 240 mm² or 1 x 630 mm² for the neutral. It retains the main switch handle, lockable open position, and compatibility with monobloc outgoing feeders and optional accessories. This model provides higher capacity and greater connection flexibility for medium-power distribution installations.

 

Principales parámetros técnicos

Main mechanical parameters

Artículo Unidad Parámetro
Corriente nominal A 1200
Dimensions (H x W x D) mm 1450 x 650 x 450
Recommended Fixing Centers (H / V) mm 520±20 / 590
Fixing Holes – 4 x M14
Transformer Power kVA 630
Recommended Cable per Phase (ALU) mm² 2 x 240 or 1 x 630
Recommended Neutral Cable (ALU) mm² 1 x 240 or 1 x 630
Fuse Type – T2 (115mm, 440V)
Barras conductoras Nm N, Ph1, Ph2, Ph3
Mounting Type – Wall-mounted
Switch Handle Position mm² Up=Closed(Red) / Down=Open(Green)
MALT Earthing Torque Nm 30±5
Handle Mounting Torque Nm 20±5
Upstream Connection Torque Nm –
Side Panels Torque Nm 30±5
Monobloc Outgoing Feeder Torque Nm 30±5

Functional Features:

  • Electrical function: suitable for a 630 kVA transformer LV main incoming/main switch; switch rated current 1200 A.

  • Connection capability: recommended phase cable 2 × 240 mm² or 1 × 630 mm² Alu; neutral cable 1 × 240 mm² or 1 × 630 mm² Alu.

  • Operation: manual switch operation; handle up = CLOSED (red), down = OPEN (green); padlocking possible in the OPEN position.

  • Safety and protection: earthing connection; side panels, horizontal protection screen, removable screen to prevent direct contact with live parts.

  • Expansion: optional EP lighting, ACG general switch, reservation panel, monobloc outgoing units, fuse protection.

  • Difference: horizontal protection screen mounted directly on the switch screen support lugs.