LW36-126/3150-40 self-energized AC high-voltage sulfur hexafl uoride circuit breaker is an outdoor product, suitable for use in power grids with an altitude of no more than 2000 meters (products with an altitude of more than 3000 meters can be designed), an ambient temperature of not less than -40℃ , and a pollution level of no more than 50Hz in AC, with a maximum voltage of 126kV in the IV level area. It is used to cut off the rated current, fault current or convert the line to achieve control and protection of the power system. It can also be used as a connecting circuit breaker.
This product uses SF6 gas as the arc extinguishing and insulating medium, adopts the most advanced international self-energized arc extinguishing technology, and is equipped with a new spring operating mechanism. It has the characteristics of long electrical life, low operating power, low noise, and high reliability. It has a simple structure, small size, and a long maintenance cycle. In the current process of power equipment tending to be oil-free and large-capacity, it can completely replace imported products of the same type.
Modelo Significado
L |
W |
36 |
– |
126 |
(W) |
I |
T |
3150 |
– |
40 |
↓ |
|
↓ |
|
|
↓ |
|
↓ |
↓ |
|
|
SF6 circuit breaker number current(kA) |
Outdoor type |
Secuencia de diseño |
|
Rated voltage (KV) |
Anti-fouling type |
|
Spring mechanism |
Corriente nominal (A) |
|
Rated short-circuit breaking |
Principales parámetros técnicos
Main mechanical parameters of circuit breaker
Artículo |
Unis |
Argumento |
Tensión nominal |
|
kV |
126 |
Rated power frequency withstand
tensión |
To ground |
|
K ·230 |
Between breaks |
|
K ·265 |
Rated lightning impulse withstand
tensión |
To ground |
kV |
K ·550 |
Between breaks |
|
K ·630 |
Power frequency withstand voltage(5min)at retailgauge pressure of SF6 gas |
|
K ·95 |
Frecuencia nominal |
Hz |
50 |
Corriente nominal |
A |
3150 |
First opening coefficient |
|
1.5 |
Corriente asignada de corte en cortocircuito |
kA |
40 |
Rated short-circuit closing current(peak value) |
|
100 |
Rated short-circuit withstand current |
kA |
40 |
Corriente nominal de pico soportada |
|
100 |
Rated short-circuit duration |
S |
4 |
Rated out-of-step breaking current |
kA |
10 |
Near-zone fault breaking current |
kA |
90%IK,75%IK |
Rated line charging breaking current |
A |
31.5 |
Rated operation sequence |
|
O-0.3s-CO-180s-CO |
Main circuit resistance |
μΩ |
≤40 |
Rated sulfur hexafluoride gas pressure (20℃ gauge pressure) |
Mpa |
0.6 |
Alarm/minimum functional pressure (20℃gauge pressure) |
Mpa |
0.55±0.03/0.50±0.03 |
Sf6 gas annual leakage rate |
|
<0.5% |
Gas moisture content (VN) |
|
≤150×10-6 |
Vida mecánica |
frecuencia |
10000 |
Radio interference level |
|
μV |
≤500 |
Creepage distance |
Between fractures |
|
3906/3150 |
To the ground |
mm |
3906/3150 |
The quality of SF6 gas filled in each unit |
kg |
10 |
The quality of each circuit breaker |
kg |
1500 |
Note: External insulation is corrected according to the altitude correction factor K: K-1.13 for every 2000m above sea level; K=1.28 for every 3000m above sea level
Principales parámetros técnicos
Main technical parameters of the mechanism
ltem |
Unis |
Argumento |
Auxiliary circuit voltage |
V |
DC220 or DC110 |
Opening and closing coil voltage/current |
VIA |
DC110/4;DC220/2 |
|
Tensión nominal |
V |
DC220、AC220/DC110、AC110 |
Energy storage motor |
Normal operating voltage range |
V |
85%~110% |
Potencia |
W |
600 |
Motor energy storage time |
S |
≤15 |
Heater and lighting circuit voltage |
V |
AC220 |
Auxiliary switch rated voltage |
V |
DC220、AC220 |
Auxiliary switch rated current |
A |
10 |
Auxiliary switch contacts |
|
10 normally open +10 normally closed |
The mechanical adjustment of the product is shown in the table below.
ltem |
Unis |
Argumento |
Center distance between circuit breaker poles |
mm |
1750 |
Moving contact stroke |
mm |
120+3 |
Moving contact contact stroke |
mm |
25*2 |
Cycle length of circuit breaker interphase operating link |
mm |
110*3 |
Velocidad de apertura |
m/s |
4.2-5m/s |
Velocidad de cierre |
m/s |
2.2-3 m/s |
Hora de apertura |
ms |
≤40 |
Hora de cierre |
ms |
≤100 |
Hora de apertura |
ms |
≤60 |
Closing-opening time |
ms |
≤80 |
Opening-closing time |
ms |
300 |
Three-phase opening phase difference |
ms |
≤2 |
Three-phase closing phase difference |
ms |
≤3 |
Structural Features
◆ The circuit breaker adopts a three-phase porcelain column single-break structure, with a spring operating mechanism for three phases, arranged in the center, and three phases in motion, so the appearance is novel and exquisite. The circuit breaker uses SF6 gas as the insulation and arc extinguishing medium. During operation, the three-pole SF6 gas of the circuit breaker is connected, and a pointer-type density relay is used to monitor its pressure and density progress. Due to the self-energy arc extinguishing principle and the optimized design in the circuit breaker movement system, the mechanical efficiency is effectively improved and the operating work is minimized;
◆ Excellent breaking performance and long electrical life;
◆ The mounting frame and support are made of high-quality steel plates that are integrally bent, and the surface treatment is all hot-dip galvanizing. All exposed fasteners are made of high-strength materials and hot-dip galvanized, or stainless steel standard parts. The mechanism box shell is made of stainless steel, so the product has excellent corrosion resistance;
◆ High mechanical reliability and can be operated frequently;
◆ Due to the inherent high insulation strength of hexacyanofuric acid gas and the optimal contact movement of the circuit breaker, the circuit breaker breaks the capacitive current without reignition;
◆ The external insulation level is high, the external insulation is designed with a large creepage distance, the creepage ratio distance ≥ 31mm/kV, and the dirt resistance is excellent. It can also operate safely in harsh environments;
◆ Strong current carrying capacity. The temperature rise test is carried out at 1.2 times the rated current of 3150A, that is, 3780A. There is still a large margin for temperature rise at each point;
◆ The overall appearance and structure of the product are compact, and on-site installation and debugging are convenient, with low maintenance workload.
Dimensiones y montaje (mm)

LW36-126 circuit breaker mass: 1500kg. Windward area: 4.7㎡